EATON - MOELLER PLN6-B10/1N-DE PLN6-B10/1N-DE 263270 Y7-263270 EATON ELECTRIC Miniature circuit breaker (MCB), 10A, 1pole+N, type B charact.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

PLN6-B10/1N-DE 263270 Y7-263270 EATON ELECTRIC Miniature circuit breaker (MCB), 10A, 1pole+N, type B charact..

PLN6-B10/1N-DE

263270

Y7-263270

EATON - MOELLER

1 Pcs.

Miniature circuit breaker (MCB), 10A, 1pole+N, type B characteristic PLN6-B10/1N-DE Eaton Moeller series xPole - PLN6 MCB. Miniature circuit breaker (MCB), 10 A, 1p+N, characteristic: B, DE Miniature circuit breaker (MCB), PLN6, 1-pole+N, tripping characteristic: B, rated current In: 10 A, rated switching capacity according to IEC/EN 60898-1: 6 kA, Switchgear for residential and commercial applications

Automation > Miniature circuit breaker (MCB)
Modular Switchgear - Tertiary

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

The PLN6-B10/1N-DE 263270 Y7-263270 EATON ELECTRIC Miniature circuit breaker (MCB), 10A, 1pole+N, type B charact.. serves as an essential protective switch designed to interrupt current flow during overloads or short circuits in electrical installations. Such miniature circuit breakers ensure enhanced safety for residential and commercial circuits. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Built-in depth (EF000218): 70.5 mm
  • Release characteristic (EF000889): B
  • Number of poles (total) (EF008618): 2
  • Number of protected poles (EF005548): 1
  • Rated current (EF000227): 10 A
  • Rated voltage (EF000228): 230 V
  • Rated insulation voltage Ui (EF001366): 440 V
  • Rated impulse withstand voltage Uimp (EF011980): 4 kV
  • Voltage type (EF000187): AC
  • Frequency (EF000416): 50 Hz
  • Power loss (EF005387): 1.9 W
  • Current limiting class (EF002568): 3
  • Flush-mounted installation (EF007517): No
  • Concurrently switching neutral conductor (EF005997): Yes
  • Over voltage category (EF002569): 3
  • Pollution degree (EF002570): 2

More info

▲

General specifications

Product Name
Eaton Moeller series xPole - PLN6 MCB
Catalog Number
263270
Model Code
PLN6-B10/1N-DE
EAN
4015082632700
Product Length/Depth
71 mm
Product Height
82 mm
Product Width
17.6 mm
Product Weight
0.13 kg
Compliances
RoHS conform

Delivery program

Number of poles (total)
2
Number of poles (protected)
1
Release characteristic
B
Amperage Rating
10 A

Technical data - electrical

Voltage type
AC
Rated operational voltage (Ue) - max
230 V
Rated insulation voltage (Ui)
440 V
Rated impulse withstand voltage (Uimp)
4 kV
Frequency rating - min
50 Hz
Frequency rating - max
60 Hz
Rated short-circuit breaking capacity (EN 60898) at 230 V
6 kA
Rated short-circuit breaking capacity (EN 60898) at 400 V
6 kA
Rated short-circuit breaking capacity (IEC 60947-2) at 230 V
0 kA
Rated short-circuit breaking capacity (IEC 60947-2) at 400 V
0 kA
Overvoltage category
III
Pollution degree
2

Technical data - mechanical

Width in number of modular spacings
1
Built-in depth
70.5 mm
Degree of protection
IP20
Connectable conductor cross section (solid-core) - min
1 mm²
Connectable conductor cross section (solid-core) - max
16 mm²
Connectable conductor cross section (multi-wired) - min
1 mm²
Connectable conductor cross section (multi-wired) - max
16 mm²

Design verification as per IEC/EN 61439 - technical data

Rated operational current for specified heat dissipation (In)
10 A
Heat dissipation per pole, current-dependent
0 W
Equipment heat dissipation, current-dependent
2.2 W
Static heat dissipation, non-current-dependent
0 W
Heat dissipation capacity
0 W
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
75 °C

Additional information

Current limiting class
3
Features
Concurrently switching N-neutral
Additional equipment possible
Special features
Ambient temperature hint: Starting at 55 °C a 1 °C increase results in a 0.5% linear reduction of current carrying capacity