An Eaton Moeller PKZM01-4-G motor-protective circuit-breaker operates as a housed switching and protection unit engineered to shield electric motors from overload currents and short circuits. Enclosed configurations like this are frequently mounted directly on machines to provide accessible local motor control and safety disconnection. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Overload release current setting (EF002336): 2.5 A
- Adjustment range undelayed short-circuit release (EF007131): 62 A
- With thermal overload protection (EF006233): No
- Phase failure sensitive (EF007400): Yes
- Switch off technique (EF007007): Thermomagnetic
- Rated operating voltage (EF001435): 690 V
- Rated permanent current Iu (EF001389): 0.63 A
- Rated operation power at AC-3, 230 V (EF007025): 0.09 kW
- Rated operation power at AC-3, 400 V (EF001364): 0.12 kW
- Power loss (EF005387): 5.33 W
- Type of electrical connection of main circuit (EF006819): Screw connection
- Type of control element (EF006976): Push button
- Device construction (EF008240): Complete device in housing
- With integrated auxiliary switch (EF001387): No
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
More info
▲General specifications
CSA Std. C22.2 No. 14
IEC 60947-4-1
VDE
VDE 0660
IEC/EN 60947
Features & Functions
Phase failure sensitive
General
Climatic environmental conditions
Terminal capacities
2 x (1 - 6) mm²
Electrical rating
Short-circuit rating
62 A, Irm, Setting range max.
Basic device fixed 15.5 x Iu, Trip Blocks