PKZM01-0,63-G 286081 Y7-286081 EATON ELECTRIC Motor-protective circuit-breaker, 3p, 0.63A, inside the enclos.. is a dedicated motor-protective circuit-breaker engineered to monitor and protect electrical motors from overloads and short circuits. Such devices disconnect power during fault conditions to extend the lifespan of industrial machinery and prevent downtime. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Overload release current setting (EF002336): 0.4 A
- Adjustment range undelayed short-circuit release (EF007131): 9.8 A
- With thermal overload protection (EF006233): No
- Phase failure sensitive (EF007400): Yes
- Switch off technique (EF007007): Thermomagnetic
- Rated operating voltage (EF001435): 690 V
- Rated permanent current Iu (EF001389): 0.63 A
- Rated operation power at AC-3, 230 V (EF007025): 0.09 kW
- Rated operation power at AC-3, 400 V (EF001364): 0.12 kW
- Power loss (EF005387): 5.16 W
- Type of electrical connection of main circuit (EF006819): Screw connection
- Type of control element (EF006976): Push button
- Device construction (EF008240): Complete device in housing
- With integrated auxiliary switch (EF001387): No
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
More info
▲General specifications
CSA Std. C22.2 No. 14
UL 508
VDE
VDE 0660
IEC/EN 60947
Features & Functions
Phase failure sensitive
General
Climatic environmental conditions
Terminal capacities
1 x (1 - 6) mm², ferrule to DIN 46228
2 x (1 - 6) mm²
Electrical rating
Short-circuit rating
± 20% tolerance, Trip blocks
Basic device fixed 15.5 x Iu, Trip Blocks