View larger
PKZM0-2,5-SPI32 199195 Y7-199195 EATON ELECTRIC PKZM0-2,5-SPI32
PKZM0-2,5-SPI32
199195
Y7-199195
EATON - MOELLER
1 Pcs.
Automation > Motor protection circuit-breaker
Circuit Breakers PKZ
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller part PKZM0-2,5-SPI32 functions as a motor-protective circuit-breaker engineered to deliver precise thermal and magnetic protection for electric motors against overloads and phase failures. These switching devices are standard in industrial automation setups for local motor control and distribution protection.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Overload release current setting (EF002336): 2.5 A
- Adjustment range undelayed short-circuit release (EF007131): 39 A
- With thermal overload protection (EF006233): false
- Phase failure sensitive (EF007400): true
- Switch off technique (EF007007): Thermomagnetic
- Rated operating voltage (EF001435): 690 V
- Rated permanent current Iu (EF001389): 2.5 A
- Rated operation power at AC-3, 230 V (EF007025): 0.37 kW
- Rated operation power at AC-3, 400 V (EF001364): 0.75 kW
- Power loss (EF005387): 5.16 W
- Type of electrical connection of main circuit (EF006819): Screw-/spring clamp connection
- Type of control element (EF006976): Turn button
- Device construction (EF008240): Built-in device fixed built-in technique
- With integrated auxiliary switch (EF001387): false
- With integrated under voltage release (EF001390): false
- Number of poles (EF001391): 3
More info
▲General specifications
VDE 0660
UL File No.: E36332
IEC/EN 60947-4-1
CSA File No.: 165628
UL Category Control No.: NLRV
UL
CSA-C22.2 No. 60947-4-1-14
CSA Class No.: 3211-05
CSA
UL 60947-4-1
CE
Features & Functions
Phase failure sensitive
General
Screw terminals on feed side
Branch circuit: Manual type E if used with terminal, or suitable for group installations, (UL/CSA)
≤ 0.25 %/K, residual error for T > 40°
-5 - 40 °C to IEC/EN 60947, VDE 0660
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Terminal capacities
2 x (1 - 6) mm², Screw terminals
1 x (1 - 6) mm², Push-in terminals
2 x (1 - 6) mm², Push-in terminals
2 x (1 - 6) mm², Push-in terminals
2 x (1 - 6) mm², Screw terminals
1 x (1 - 6) mm², Push-in terminals
2 x (1 - 6) mm², Push-in terminals
18 - 8, Push-in terminals
Electrical rating
Short-circuit rating
50 kA, 600 V High Fault, CB, SCCR (UL/CSA) with 600 A, 600 V High Fault, CB, SCCR (UL/CSA)
65 kA, 240 V, SCCR (UL/CSA)
65 kA, 480 Y/277 V, SCCR (UL/CSA)
38.8 A, Irm, Setting range max.
Basic device fixed 15.5 x Iu, Trip Blocks