View larger
PKZM0-25-PI 199161 Y7-199161 EATON ELECTRIC Motor protector switch 3 poles Ir 20-25 A Screw connection
PKZM0-25-PI
199161
Y7-199161
EATON - MOELLER
1 Pcs.
Automation > Motor protection circuit-breaker
Circuit Breakers PKZ
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Eaton Moeller motor protector switch (PKZM0-25-PI) serves as a specialized manual controller designed to protect electric motors from overloads, short circuits, and phase imbalances. These devices combine manual switching and thermal-magnetic trip functions within a single housing for industrial applications.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Overload release current setting (EF002336): 25 A
- Adjustment range undelayed short-circuit release (EF007131): 388 A
- With thermal overload protection (EF006233): No
- Phase failure sensitive (EF007400): Yes
- Switch off technique (EF007007): Thermomagnetic
- Rated operating voltage (EF001435): 690 V
- Rated permanent current Iu (EF001389): 25 A
- Rated operation power at AC-3, 230 V (EF007025): 5.5 kW
- Rated operation power at AC-3, 400 V (EF001364): 12.5 kW
- Power loss (EF005387): 7.04 W
- Type of electrical connection of main circuit (EF006819): Spring clamp connection
- Type of control element (EF006976): Rotating button
- Device construction (EF008240): Built-in device fixed built-in technique
- With integrated auxiliary switch (EF001387): No
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
More info
▲General specifications
VDE 0660
UL
CSA
IEC/EN 60947-4-1
UL 60947-4-1
CSA-C22.2 No. 60947-4-1-14
CE
UL File No.: E36332
UL Category Control No.: NLRV
CSA File No.: 165628
CSA Class No.: 3211-05
Features & Functions
Phase failure sensitive
General
Branch circuit: Manual type E in combination with contactor DILM and terminal BK25/3-PKZ0-E, or suitable for group installations, (UL/CSA)
-5 - 40 °C to IEC/EN 60947, VDE 0660
≤ 0.25 %/K, residual error for T > 40°
Climatic environmental conditions
Damp heat, cyclic, to IEC 60068-2-30
Terminal capacities
2 x (1 - 6) mm², Push-in terminals
2 x (1 - 6) mm²
2 x (1 - 6) mm²
Electrical rating
Short-circuit rating
10 kA, 600 V High Fault, CB, SCCR (UL/CSA) with 125 A, 600 V High Fault, CB, SCCR (UL/CSA)
18 kA, 600 V High Fault, Fuse with CL, SCCR (UL/CSA) with 600 A, 600 V High Fault, Fuse with CL, SCCR (UL/CSA)
18 kA, 600 V High Fault, CB with CL, SCCR (UL/CSA) with 600 A, 600 V High Fault, CB with CL, SCCR (UL/CSA)
18 kA, 480 V High Fault, CB, SCCR (UL/CSA) with 600 A, 480 V High Fault, CB, SCCR (UL/CSA)
18 kA, 480 V High Fault, Fuse, SCCR (UL/CSA) with 600 A, 480 V High Fault, Fuse, SCCR (UL/CSA)
18 kA, 480 Y/277 V, SCCR (UL/CSA) with contactor DILM25
388 A, Irm, Setting range max.
Basic device fixed 15.5 x Iu, Trip Blocks