View larger
PKZM0-25/NHI11 039430 Y7-39430 EATON ELECTRIC Motor-protective circuit-breaker, 3p+1N/O+1N/C, Ir 20-25A, scr..
PKZM0-25/NHI11
039430
Y7-39430
EATON - MOELLER
1 Pcs.
Automation > Motor protection circuit-breaker
Circuit Breakers PKZ
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Eaton Moeller PKZM0-25/NHI11 039430 Y7-39430 EATON ELECTRIC Motor-protective circuit-breaker, 3p+1N/O+1N/C, Ir 20-25A, scr.. safeguards electric motors by combining manual switching functions with precise thermal and magnetic trip mechanisms. These protective breakers are widely installed in industrial automation setups to prevent motor burnout.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Overload release current setting (EF002336): 20 A
- Adjustment range undelayed short-circuit release (EF007131): 388 A
- With thermal overload protection (EF006233): No
- Phase failure sensitive (EF007400): Yes
- Switch off technique (EF007007): Thermomagnetic
- Rated operating voltage (EF001435): 690 V
- Rated permanent current Iu (EF001389): 25 A
- Rated operation power at AC-3, 230 V (EF007025): 5.5 kW
- Rated operation power at AC-3, 400 V (EF001364): 12.5 kW
- Power loss (EF005387): 7.04 W
- Type of electrical connection of main circuit (EF006819): Screw connection
- Type of control element (EF006976): Rotating button
- Device construction (EF008240): Built-in device fixed built-in technique
- With integrated auxiliary switch (EF001387): Yes
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
More info
▲General specifications
UL
UL Category Control No.: NLRV
UL 60947-4-1
IEC/EN 60947
CSA
IEC/EN 60947-4-1
CSA-C22.2 No. 60947-4-1-14
CSA Class No.: 3211-05
VDE 0660
UL File No.: E36332
CE
Features & Functions
Phase failure sensitive
General
Ex II (2) G [Ex eb Gb] [Ex db Gb] [Ex pxb Gb]
Ex II (2) D [Ex tb Db] [Ex pxb Db]
Also motors with efficiency class IE3
-25 - 55 °C, Operating range
≤ 0.25 %/K, residual error for T > 40°
Climatic environmental conditions
Damp heat, cyclic, to IEC 60068-2-30
Terminal capacities
2 x (0.75 - 2.5) mm², Control circuit cables
18 - 14
1 Nm, Screw terminals, Control circuit cables
Electrical rating
Short-circuit rating
10 kA, 600 V High Fault, CB, SCCR (UL/CSA) with 125 A, 600 V High Fault, CB, SCCR (UL/CSA)
18 kA, 600 V High Fault, Fuse with CL, SCCR (UL/CSA) with 600 A, 600 V High Fault, Fuse with CL, SCCR (UL/CSA)
18 kA, 600 V High Fault, CB with CL, SCCR (UL/CSA) with 600 A, 600 V High Fault, CB with CL, SCCR (UL/CSA)
18 kA, 480 V High Fault, CB, SCCR (UL/CSA) with 600 A, 480 V High Fault, CB, SCCR (UL/CSA)
18 kA, 480 V High Fault, Fuse, SCCR (UL/CSA) with 600 A, 480 V High Fault, Fuse, SCCR (UL/CSA)
18 kA, 480 Y/277 V, SCCR (UL/CSA) with contactor DILM25
Basic device fixed 15.5 x Iu, Trip Blocks
± 20% tolerance, Trip blocks