View larger
PKZM0-25/AK 265344 Y7-265344 EATON ELECTRIC Motor-protective circuit-breaker, 3p, Ir 20-25A, thumb grip lock..
PKZM0-25/AK
265344
Y7-265344
EATON - MOELLER
1 Pcs.
Automation > Motor protection circuit-breaker
Circuit Breakers PKZ
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Providing dependable operational safeguarding, the Eaton Moeller PKZM0-25/AK motor-protective circuit-breaker protects industrial electrical motors from phase loss, overloads, and short circuits. These devices ensure smooth machine automation by preventing thermal damage to drive systems.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Overload release current setting (EF002336): 20 A
- Adjustment range undelayed short-circuit release (EF007131): 388 A
- With thermal overload protection (EF006233): No
- Phase failure sensitive (EF007400): Yes
- Switch off technique (EF007007): Thermomagnetic
- Rated operating voltage (EF001435): 690 V
- Rated permanent current Iu (EF001389): 25 A
- Rated operation power at AC-3, 230 V (EF007025): 5.5 kW
- Rated operation power at AC-3, 400 V (EF001364): 12.5 kW
- Power loss (EF005387): 7.04 W
- Type of electrical connection of main circuit (EF006819): Screw connection
- Type of control element (EF006976): Rotating button
- Device construction (EF008240): Built-in device fixed built-in technique
- With integrated auxiliary switch (EF001387): No
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
More info
▲General specifications
UL Category Control No.: NLRV
VDE 0660
CSA-C22.2 No. 60947-4-1-14
IEC/EN 60947
CSA File No.: 165628
UL File No.: E36332
IEC/EN 60947-4-1
UL 60947-4-1
CSA
UL
CSA Class No.: 3211-05
Features & Functions
Motor protection
General
Also motors with efficiency class IE3
≤ 0.25 %/K, residual error for T > 40°
-25 - 55 °C, Operating range
Climatic environmental conditions
Damp heat, cyclic, to IEC 60068-2-30
Terminal capacities
2 x (1 - 6) mm², ferrule to DIN 46228
2 x (1 - 6) mm²
1.7 Nm, Screw terminals, Main cable
Electrical rating
Short-circuit rating
10 kA, 600 V High Fault, CB, SCCR (UL/CSA) with 125 A, 600 V High Fault, CB, SCCR (UL/CSA)
18 kA, 600 V High Fault, Fuse with CL, SCCR (UL/CSA) with 600 A, 600 V High Fault, Fuse with CL, SCCR (UL/CSA)
18 kA, 600 V High Fault, CB with CL, SCCR (UL/CSA) with 600 A, 600 V High Fault, CB with CL, SCCR (UL/CSA)
18 kA, 480 V High Fault, CB, SCCR (UL/CSA) with 600 A, 480 V High Fault, CB, SCCR (UL/CSA)
18 kA, 480 V High Fault, Fuse, SCCR (UL/CSA) with 600 A, 480 V High Fault, Fuse, SCCR (UL/CSA)
18 kA, 480 Y/277 V, SCCR (UL/CSA) with contactor DILM25
± 20% tolerance, Trip blocks
Basic device fixed 15.5 x Iu, Trip Blocks