View larger
PKZM0-16/NHI11 039423 Y7-39423 EATON ELECTRIC Motor-protective circuit-breaker, 3p+1N/O+1N/C, Ir 10-16A, scr..
PKZM0-16/NHI11
039423
Y7-39423
EATON - MOELLER
1 Pcs.
Automation > Motor protection circuit-breaker
Circuit Breakers PKZ
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller PKZM0-16/NHI11 motor-protective circuit-breaker offers dependable switching, short-circuit protection, and auxiliary signaling capabilities for industrial motor circuits. Electrical contractors install these versatile three-pole units to safely manage motor loads while providing immediate status feedback to control systems. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Manufacturer: Eaton Moeller
- Manufacturer part number: PKZM0-16/NHI11
- Catalogue code: 039423
- Catalogue title: PKZM0-16/NHI11 039423 Y7-39423 EATON ELECTRIC Motor-protective circuit-breaker, 3p+1N/O+1N/C, Ir 10-16A, scr..
- Product description: General specifications Product Name Eaton Moeller series PKZM0 Motor-protective circuit-breaker Catalog Number 039423 Model Code PKZM0-16/NHI11 EAN 4015080394235 Product Length/Depth 76 mm Product Height 93 mm Product W
- Manufacturer summary: Motor-protective circuit-breaker, 3p+1N/O+1N/C, Ir=10-16A, screw connection Switch motor protector; 3 pole + 1 NO + 1 NC; Ir=10-16 A; Connection to screw Eaton Moeller series PKZM0 Motor-protective circuit-breaker, 3p+1
More info
▲General specifications
UL 60947-4-1
UL File No.: E36332
VDE 0660
UL
CE
CSA Class No.: 3211-05
IEC/EN 60947
CSA File No.: 165628
CSA-C22.2 No. 60947-4-1-14
CSA
UL Category Control No.: NLRV
Features & Functions
Motor protection
General
Also motors with efficiency class IE3
≤ 0.25 %/K, residual error for T > 40°
-25 - 55 °C, Operating range
Climatic environmental conditions
Damp heat, cyclic, to IEC 60068-2-30
Terminal capacities
2 x (0.75 - 1.5) mm²
2 x (0.75 - 2.5) mm², Control circuit cables
18 - 10
1 Nm, Screw terminals, Control circuit cables
Electrical rating
Short-circuit rating
10 kA, 600 V High Fault, CB, SCCR (UL/CSA) with 125 A, 600 V High Fault, CB, SCCR (UL/CSA)
50 kA, 600 V High Fault, CB with CL, SCCR (UL/CSA) with 600 A, 600 V High Fault, CB with CL, SCCR (UL/CSA)
50 kA, 600 V High Fault, Fuse with CL, SCCR (UL/CSA) with 600 A, 600 V High Fault, Fuse with CL, SCCR (UL/CSA)
18 kA, 480 V High Fault, CB, SCCR (UL/CSA) with 600 A, 480 V High Fault, CB, SCCR (UL/CSA)
18 kA, 480 V High Fault, Fuse, SCCR (UL/CSA) with 600 A, 480 V High Fault, Fuse, SCCR (UL/CSA)
65 kA, 480 Y/277 V, SCCR (UL/CSA) with contactor DILM17
Basic device fixed 15.5 x Iu, Trip Blocks
± 20% tolerance, Trip blocks