View larger
PKZM0-1,6/NHI-E-10-MTB 210205 Y7-210205 EATON ELECTRIC Motor-Protective Circuit-Breakers 3-pole + 1 N/O Ir 1..
PKZM0-1,6/NHI-E-10-MTB
210205
Y7-210205
EATON - MOELLER
38 Pcs.
Automation > Motor protection circuit-breaker
Circuit Breakers PKZ
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Motor-Protective Circuit-Breakers part number PKZM0-1,6/NHI-E-10-MTB from Eaton Moeller provides dependable current management and localized switching for automation setups. Such components are routinely installed within control cabinets to shield machinery against operational overloads and short circuits.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Overload release current setting (EF002336): 1 A
- Adjustment range undelayed short-circuit release (EF007131): 25 A
- With thermal overload protection (EF006233): No
- Phase failure sensitive (EF007400): Yes
- Switch off technique (EF007007): Thermomagnetic
- Rated operating voltage (EF001435): 690 V
- Rated permanent current Iu (EF001389): 1.6 A
- Rated operation power at AC-3, 230 V (EF007025): 0.25 kW
- Rated operation power at AC-3, 400 V (EF001364): 0.55 kW
- Power loss (EF005387): 5.36 W
- Type of electrical connection of main circuit (EF006819): Screw connection
- Type of control element (EF006976): Rotating button
- Device construction (EF008240): Built-in device fixed built-in technique
- With integrated auxiliary switch (EF001387): Yes
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
More info
▲Delivery program
IE3-ready devices are identified by the logo on their packaging.
Observe manual MN03402003Z-DE/EN.
Can be snapped on to IEC/EN 60715 top-hat rail with 7.5 or 15 mm height.
Technical data
Damp heat, cyclic, to IEC 60068-2-30
2 x (1 - 6) mm2
2 x (1 - 6) mm2
2 x (0.75…1) mm2
2 x (0.75…1.5) mm2
208 V
240 V
480 V
600 V
240 V
Design verification as per IEC/EN 61439
Technical data ETIM 7.0
Approvals
Characteristics
2: Trip-indicating auxiliary contact
3: Shunt releases, undervoltage releases
1: Minimum level, 3-phase
2: Maximum level, 3-phase
3: Minimum marker, 2-phase
4: Highest marker, 2-phase
Let-through energy