View larger
PKZM0-16/AK 265342 Y7-265342 EATON ELECTRIC Motor-protective circuit-breaker, 3p, Ir 10-16A, thumb grip lock..
PKZM0-16/AK
265342
Y7-265342
EATON - MOELLER
1 Pcs.
Automation > Motor protection circuit-breaker
Circuit Breakers PKZ
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Eaton Moeller PKZM0-16/AK motor-protective circuit-breaker functions as an electromechanical switching and protection device designed to safeguard electrical motors against thermal overloads and short circuits. Units of this type are commonly installed in industrial control panels to manage motor starting operations safely while disconnecting power during fault conditions. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Overload release current setting (EF002336): 10 A
- Adjustment range undelayed short-circuit release (EF007131): 248 A
- With thermal overload protection (EF006233): No
- Phase failure sensitive (EF007400): Yes
- Switch off technique (EF007007): Thermomagnetic
- Rated operating voltage (EF001435): 690 V
- Rated permanent current Iu (EF001389): 16 A
- Rated operation power at AC-3, 230 V (EF007025): 4 kW
- Rated operation power at AC-3, 400 V (EF001364): 7.5 kW
- Power loss (EF005387): 6.43 W
- Type of electrical connection of main circuit (EF006819): Screw connection
- Type of control element (EF006976): Rotating button
- Device construction (EF008240): Built-in device fixed built-in technique
- With integrated auxiliary switch (EF001387): No
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
More info
▲General specifications
UL 60947-4-1
IEC/EN 60947-4-1
UL Category Control No.: NLRV
CSA
CSA-C22.2 No. 60947-4-1-14
UL File No.: E36332
VDE 0660
UL
CE
IEC/EN 60947
CSA Class No.: 3211-05
Features & Functions
Phase failure sensitive
General
Also motors with efficiency class IE3
≤ 0.25 %/K, residual error for T > 40°
-25 - 55 °C, Operating range
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Terminal capacities
2 x (1 - 6) mm², ferrule to DIN 46228
1 x (1 - 6) mm²
1.7 Nm, Screw terminals, Main cable
Electrical rating
Short-circuit rating
10 kA, 600 V High Fault, CB, SCCR (UL/CSA) with 125 A, 600 V High Fault, CB, SCCR (UL/CSA)
50 kA, 600 V High Fault, CB with CL, SCCR (UL/CSA) with 600 A, 600 V High Fault, CB with CL, SCCR (UL/CSA)
50 kA, 600 V High Fault, Fuse with CL, SCCR (UL/CSA) with 600 A, 600 V High Fault, Fuse with CL, SCCR (UL/CSA)
18 kA, 480 V High Fault, CB, SCCR (UL/CSA) with 600 A, 480 V High Fault, CB, SCCR (UL/CSA)
18 kA, 480 V High Fault, Fuse, SCCR (UL/CSA) with 600 A, 480 V High Fault, Fuse, SCCR (UL/CSA)
65 kA, 480 Y/277 V, SCCR (UL/CSA) with contactor DILM17
186 A, Irm, Setting range max.
± 20% tolerance, Trip blocks