View larger
PKZM0-12-PI 199158 Y7-199158 EATON ELECTRIC Motor protector switch 3 poles Ir 8-12 A Screw connection
PKZM0-12-PI
199158
Y7-199158
EATON - MOELLER
1 Pcs.
Automation > Motor protection circuit-breaker
Circuit Breakers PKZ
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller PKZM0-12-PI motor protector switch 3 poles Ir 8-12 A Screw connection functions as a dedicated switching and protective device designed to safeguard industrial electric motors against overloads, phase failures, and short circuits. These compact units are routinely integrated into electrical control panels to provide reliable manual starting, stopping, and fault interruption for machinery. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Overload release current setting (EF002336): 12 A
- Adjustment range undelayed short-circuit release (EF007131): 186 A
- With thermal overload protection (EF006233): No
- Phase failure sensitive (EF007400): Yes
- Switch off technique (EF007007): Thermomagnetic
- Rated operating voltage (EF001435): 690 V
- Rated permanent current Iu (EF001389): 12 A
- Rated operation power at AC-3, 230 V (EF007025): 3 kW
- Rated operation power at AC-3, 400 V (EF001364): 5.5 kW
- Power loss (EF005387): 6.64 W
- Type of electrical connection of main circuit (EF006819): Spring clamp connection
- Type of control element (EF006976): Rotating button
- Device construction (EF008240): Built-in device fixed built-in technique
- With integrated auxiliary switch (EF001387): No
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
More info
▲General specifications
VDE 0660
UL
CSA
IEC/EN 60947-4-1
UL 60947-4-1
CSA-C22.2 No. 60947-4-1-14
CE
UL File No.: E36332
UL Category Control No.: NLRV
CSA File No.: 165628
CSA Class No.: 3211-05
Features & Functions
Phase failure sensitive
General
Branch circuit: Manual type E if used with terminal, or suitable for group installations, (UL/CSA)
-25 - 55 °C, Operating range
≤ 0.25 %/K, residual error for T > 40°
Climatic environmental conditions
Damp heat, cyclic, to IEC 60068-2-30
Terminal capacities
Electrical rating
Short-circuit rating
18 kA, 600 V High Fault, CB, SCCR (UL/CSA) with 600 A, 600 V High Fault, Fuse, SCCR (UL/CSA)
65 kA, 480 V High Fault, Fuse, SCCR (UL/CSA) with 600 A, 480 V High Fault, Fuse, SCCR (UL/CSA)
65 kA, 480 V High Fault, CB, SCCR (UL/CSA) with 600 A, 480 V High Fault, CB, SCCR (UL/CSA)
18 kA, 480 Y/277 V, SCCR (UL/CSA)
18 kA, 600 Y/347 V, SCCR (UL/CSA)
65 kA, 240 V, SCCR (UL/CSA)
65 kA, 480 Y/277 V, SCCR (UL/CSA)
186 A, Irm, Setting range max.
± 20% tolerance, Trip blocks