View larger
PKZM0-10-SPI32 199198 Y7-199198 EATON ELECTRIC PKZM0-10-SPI32
PKZM0-10-SPI32
199198
Y7-199198
EATON - MOELLER
1 Pcs.
Automation > Motor protection circuit-breaker
Circuit Breakers PKZ
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Designed for control panel installations, the Eaton Moeller PKZM0-10-SPI32 199198 Y7-199198 EATON ELECTRIC PKZM0-10-SPI32 protects electric motors against thermal overloads and short circuits while allowing manual switching. This unit ensures dependable operational safety in industrial environments.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Overload release current setting (EF002336): 10 A
- Adjustment range undelayed short-circuit release (EF007131): 155 A
- With thermal overload protection (EF006233): No
- Phase failure sensitive (EF007400): Yes
- Switch off technique (EF007007): Thermomagnetic
- Rated operating voltage (EF001435): 690 V
- Rated permanent current Iu (EF001389): 10 A
- Rated operation power at AC-3, 230 V (EF007025): 2.2 kW
- Rated operation power at AC-3, 400 V (EF001364): 4 kW
- Power loss (EF005387): 6.48 W
- Type of electrical connection of main circuit (EF006819): Screw-/spring clamp connection
- Type of control element (EF006976): Rotating button
- Device construction (EF008240): Built-in device fixed built-in technique
- With integrated auxiliary switch (EF001387): No
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
More info
▲General specifications
IEC/EN 60947
UL File No.: E36332
IEC/EN 60947-4-1
CSA File No.: 165628
UL Category Control No.: NLRV
UL
CSA-C22.2 No. 60947-4-1-14
CSA Class No.: 3211-05
CSA
UL 60947-4-1
CE
Features & Functions
Phase failure sensitive
General
Branch circuit: Manual type E if used with terminal, or suitable for group installations, (UL/CSA)
-25 - 55 °C, Operating range
≤ 0.25 %/K, residual error for T > 40°
Climatic environmental conditions
Damp heat, cyclic, to IEC 60068-2-30
Terminal capacities
Electrical rating
Short-circuit rating
30 kA, 600 V High Fault, Fuse, SCCR (UL/CSA) with 600 A, 600 V High Fault, Fuse, SCCR (UL/CSA)
30 kA, 600 V High Fault, CB, SCCR (UL/CSA) with 600 A, 600 V High Fault, CB, SCCR (UL/CSA)
65 kA, 240 V, SCCR (UL/CSA)
65 kA, 480 Y/277 V, SCCR (UL/CSA)
± 20% tolerance, Trip blocks
155 A, Irm, Setting range max.
Motor rating
Communication
Screw terminals on feed side