PKZM0-10/NHI11 039424 Y7-39424 EATON ELECTRIC Motor-protective circuit-breaker, 3p+1N/O+1N/C, Ir 6.3-10A, sc..
PKZM0-10/NHI11
039424
Y7-39424
EATON - MOELLER
1 Pcs.
Automation > Motor protection circuit-breaker
Circuit Breakers PKZ
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Featuring integrated auxiliary contacts, this Eaton Moeller PKZM0-10/NHI11 motor-protective circuit-breaker offers comprehensive safeguarding and status signaling for electric motors. Industrial control panels rely on these compact units to prevent motor damage from overloads while providing vital feedback signals. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Overload release current setting (EF002336): 6.3 A
- Adjustment range undelayed short-circuit release (EF007131): 155 A
- With thermal overload protection (EF006233): No
- Phase failure sensitive (EF007400): Yes
- Switch off technique (EF007007): Thermomagnetic
- Rated operating voltage (EF001435): 690 V
- Rated permanent current Iu (EF001389): 10 A
- Rated operation power at AC-3, 230 V (EF007025): 2.2 kW
- Rated operation power at AC-3, 400 V (EF001364): 4 kW
- Power loss (EF005387): 6.48 W
- Type of electrical connection of main circuit (EF006819): Screw connection
- Type of control element (EF006976): Rotating button
- Device construction (EF008240): Built-in device fixed built-in technique
- With integrated auxiliary switch (EF001387): Yes
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
More info
▲General specifications
UL 60947-4-1
UL File No.: E36332
UL
CE
CSA File No.: 165628
CSA
CSA Class No.: 3211-05
CSA-C22.2 No. 60947-4-1-14
VDE 0660
IEC/EN 60947-4-1
UL Category Control No.: NLRV
Features & Functions
Motor protection
General
Branch circuit: Manual type E if used with terminal, or suitable for group installations, (UL/CSA)
≤ 0.25 %/K, residual error for T > 40°
-5 - 40 °C to IEC/EN 60947, VDE 0660
Climatic environmental conditions
Damp heat, cyclic, to IEC 60068-2-30
Terminal capacities
2 x (0.75 - 1.5) mm²
1 x (0.75 - 2.5) mm², Control circuit cables
18 - 14
1.7 Nm, Screw terminals, Main cable
Electrical rating
Short-circuit rating
30 kA, 600 V High Fault, Fuse, SCCR (UL/CSA) with 600 A, 600 V High Fault, Fuse, SCCR (UL/CSA)
30 kA, 600 V High Fault, CB, SCCR (UL/CSA) with 600 A, 600 V High Fault, CB, SCCR (UL/CSA)
50 kA, 600 Y/347 V, SCCR (UL/CSA)
65 kA, 240 V, SCCR (UL/CSA)
Accessories required BK25/3-PKZ0-E
± 20% tolerance, Trip blocks
Basic device fixed 15.5 x Iu, Trip Blocks