View larger
PKZM0-1/NHI11 039429 Y7-39429 EATON ELECTRIC Motor-protective circuit-breaker, 3p+1N/O+1N/C, Ir 0.63-1A, scr..
PKZM0-1/NHI11
039429
Y7-39429
EATON - MOELLER
1 Pcs.
Automation > Motor protection circuit-breaker
Circuit Breakers PKZ
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Equipped with auxiliary contacts, the PKZM0-1/NHI11 Eaton Moeller motor-protective circuit-breaker safeguards small electric motors while providing feedback signals to control systems. Motor protection switches combine overload and short-circuit monitoring to protect critical manufacturing equipment from electrical faults. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Overload release current setting (EF002336): 0.63 A
- Adjustment range undelayed short-circuit release (EF007131): 15.5 A
- With thermal overload protection (EF006233): No
- Phase failure sensitive (EF007400): Yes
- Switch off technique (EF007007): Thermomagnetic
- Rated operating voltage (EF001435): 690 V
- Rated permanent current Iu (EF001389): 1 A
- Rated operation power at AC-3, 230 V (EF007025): 0.12 kW
- Rated operation power at AC-3, 400 V (EF001364): 0.25 kW
- Power loss (EF005387): 5.33 W
- Type of electrical connection of main circuit (EF006819): Screw connection
- Type of control element (EF006976): Rotating button
- Device construction (EF008240): Built-in device fixed built-in technique
- With integrated auxiliary switch (EF001387): Yes
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
More info
▲General specifications
VDE 0660
CSA-C22.2 No. 60947-4-1-14
CSA Class No.: 3211-05
IEC/EN 60947
IEC/EN 60947-4-1
UL Category Control No.: NLRV
CSA
UL File No.: E36332
CSA File No.: 165628
CE
UL
Features & Functions
Phase failure sensitive
General
Branch circuit: Manual type E if used with terminal, or suitable for group installations, (UL/CSA)
≤ 0.25 %/K, residual error for T > 40°
-5 - 40 °C to IEC/EN 60947, VDE 0660
Climatic environmental conditions
Damp heat, cyclic, to IEC 60068-2-30
Terminal capacities
2 x (0.75 - 1.5) mm²
1 x (0.75 - 2.5) mm², Control circuit cables
18 - 14
1.7 Nm, Screw terminals, Main cable
Electrical rating
Short-circuit rating
50 kA, 600 V High Fault, CB, SCCR (UL/CSA) with 600 A, 600 V High Fault, CB, SCCR (UL/CSA)
65 kA, 240 V, SCCR (UL/CSA)
65 kA, 480 Y/277 V, SCCR (UL/CSA)
Accessories required BK25/3-PKZ0-E
Basic device fixed 15.5 x Iu, Trip Blocks
15.5 A, Irm, Setting range max.