View larger
PKZM0-0,63-SPI16 199180 Y7-199180 EATON ELECTRIC PKZM0-0,63-SPI16
PKZM0-0,63-SPI16
199180
Y7-199180
EATON - MOELLER
1 Pcs.
Automation > Motor protection circuit-breaker
Circuit Breakers PKZ
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Eaton Moeller PKZM0-0,63-SPI16 motor starter protector combines manual switching functionality with adjustable thermal and magnetic trip mechanisms to safeguard small electric motors. It protects industrial machinery from overloads and short circuits efficiently.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Overload release current setting (EF002336): 0.63 A
- Adjustment range undelayed short-circuit release (EF007131): 9.8 A
- With thermal overload protection (EF006233): No
- Phase failure sensitive (EF007400): Yes
- Switch off technique (EF007007): Thermomagnetic
- Rated operating voltage (EF001435): 690 V
- Rated permanent current Iu (EF001389): 0.63 A
- Rated operation power at AC-3, 230 V (EF007025): 0.09 kW
- Rated operation power at AC-3, 400 V (EF001364): 0.12 kW
- Power loss (EF005387): 5.16 W
- Type of electrical connection of main circuit (EF006819): Screw-/spring clamp connection
- Type of control element (EF006976): Rotating button
- Device construction (EF008240): Built-in device fixed built-in technique
- With integrated auxiliary switch (EF001387): No
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
More info
▲General specifications
IEC/EN 60947
UL File No.: E36332
IEC/EN 60947-4-1
CSA File No.: 165628
UL Category Control No.: NLRV
UL
CSA-C22.2 No. 60947-4-1-14
CSA Class No.: 3211-05
CSA
UL 60947-4-1
CE
Features & Functions
Motor protection
General
Branch circuit: Manual type E if used with terminal, or suitable for group installations, (UL/CSA)
≤ 0.25 %/K, residual error for T > 40°
-25 - 55 °C, Operating range
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Terminal capacities
2 x (1 - 6) mm², Screw terminals
1 x (0.5 - 2.5) mm², Push-in terminals, ferrule to DIN 46228-1
2 x (0.5 - 2.5) mm², Push-in terminals, ferrule to DIN 46228-1
1 x (0.5 - 1.5) mm², Push-in terminals, ferrule to DIN 46228-4
2 x (0.5 - 1.5) mm², Push-in terminals, ferrule to DIN 46228-4
2 x (0.5 - 2.5) mm², Push-in terminals
2 x (0.5 - 2.5) mm², Push-in terminals
20 - 14, Push-in terminals
Electrical rating
Short-circuit rating
50 kA, 600 V High Fault, CB, SCCR (UL/CSA) with 600 A, 600 V High Fault, CB, SCCR (UL/CSA)
65 kA, 240 V, SCCR (UL/CSA)
65 kA, 480 Y/277 V, SCCR (UL/CSA)
Basic device fixed 15.5 x Iu, Trip Blocks
± 20% tolerance, Trip blocks
Communication
Push-in terminals on output side