View larger
PKZM0-0,63-SC/AK 265348 XTPRSCP63BC1 EATON ELECTRIC Motor-Protective Circuit-Breakers, 3-pole, Ir 0.63 1 A, ..
PKZM0-0,63-SC/AK
265348
XTPRSCP63BC1
EATON - MOELLER
1 Pcs.
Automation > Motor protection circuit-breaker
Circuit Breakers PKZ
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Designed for precision motor defense, the Eaton Moeller PKZM0-0,63-SC/AK protects low-voltage circuits from thermal overloads and instantaneous short circuits. Such devices are typically mounted inside electrical panels to isolate faulty loads and protect connected industrial machinery from damage. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Overload release current setting (EF002336): 0.4 A
- Adjustment range undelayed short-circuit release (EF007131): 9.8 A
- With thermal overload protection (EF006233): No
- Phase failure sensitive (EF007400): Yes
- Switch off technique (EF007007): Thermomagnetic
- Rated operating voltage (EF001435): 690 V
- Rated permanent current Iu (EF001389): 0.63 A
- Rated operation power at AC-3, 230 V (EF007025): 0.09 kW
- Rated operation power at AC-3, 400 V (EF001364): 0.12 kW
- Power loss (EF005387): 5.16 W
- Type of electrical connection of main circuit (EF006819): Screw connection
- Type of control element (EF006976): Rotating button
- Device construction (EF008240): Built-in device fixed built-in technique
- With integrated auxiliary switch (EF001387): No
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
More info
▲General specifications
IEC/EN 60947-4-1
UL File No.: E36332
CSA
CSA Class No.: 3211-05
CSA-C22.2 No. 60947-4-1-14
UL 60947-4-1
CE
UL
VDE 0660
IEC/EN 60947
CSA File No.: 165628
Features & Functions
Phase failure sensitive
General
≤ 0.25 %/K, residual error for T > 40°
-25 - 55 °C, Operating range
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Terminal capacities
1 x (1 - 6) mm², ferrule to DIN 46228, Screw terminals
1 x (0.75 - 2.5) mm², without ferrule, Spring-loaded terminals
2 x (0.75 - 2.5) mm², without ferrule, Spring-loaded terminals
1 x (0.75 - 2.5) mm², ferrule to DIN 46228, Spring-loaded terminals
2 x (0.75 - 2.5) mm², Spring-loaded terminals
Electrical rating
Short-circuit rating
Basic device fixed 15.5 x Iu, Trip Blocks
± 20% tolerance, Trip blocks
Communication
Spring-cage terminals on output side