View larger
PKZM0-0,25-SPI16 199178 Y7-199178 EATON ELECTRIC PKZM0-0,25-SPI16
PKZM0-0,25-SPI16
199178
Y7-199178
EATON - MOELLER
1 Pcs.
Automation > Motor protection circuit-breaker
Circuit Breakers PKZ
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller PKZM0-0,25-SPI16 is a compact motor protection switch engineered to safeguard low-current electrical motors against phase loss and overloads. Motor protection switches provide reliable switching, isolation, and thermal-magnetic trip capabilities for industrial automation drives.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Overload release current setting (EF002336): 0.25 A
- Adjustment range undelayed short-circuit release (EF007131): 3.9 A
- With thermal overload protection (EF006233): No
- Phase failure sensitive (EF007400): Yes
- Switch off technique (EF007007): Thermomagnetic
- Rated operating voltage (EF001435): 690 V
- Rated permanent current Iu (EF001389): 0.25 A
- Rated operation power at AC-3, 230 V (EF007025): 0 kW
- Rated operation power at AC-3, 400 V (EF001364): 0.06 kW
- Power loss (EF005387): 5.15 W
- Type of electrical connection of main circuit (EF006819): Screw-/spring clamp connection
- Type of control element (EF006976): Rotating button
- Device construction (EF008240): Built-in device fixed built-in technique
- With integrated auxiliary switch (EF001387): No
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
More info
▲General specifications
IEC/EN 60947
UL File No.: E36332
IEC/EN 60947-4-1
CSA File No.: 165628
UL Category Control No.: NLRV
UL
CSA-C22.2 No. 60947-4-1-14
CSA Class No.: 3211-05
CSA
UL 60947-4-1
CE
Features & Functions
Phase failure sensitive
General
Branch circuit: Manual type E if used with terminal, or suitable for group installations, (UL/CSA)
-5 - 40 °C to IEC/EN 60947, VDE 0660
≤ 0.25 %/K, residual error for T > 40°
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Terminal capacities
2 x (1 - 6) mm², Screw terminals
1 x (0.5 - 2.5) mm², Push-in terminals, ferrule to DIN 46228-1
2 x (0.5 - 2.5) mm², Push-in terminals, ferrule to DIN 46228-1
1 x (0.5 - 1.5) mm², Push-in terminals, ferrule to DIN 46228-4
2 x (0.5 - 1.5) mm², Push-in terminals, ferrule to DIN 46228-4
2 x (0.5 - 2.5) mm², Push-in terminals
2 x (0.5 - 2.5) mm², Push-in terminals
20 - 14, Push-in terminals
Electrical rating
Short-circuit rating
50 kA, 600 V High Fault, CB, SCCR (UL/CSA) with 600 A, 600 V High Fault, CB, SCCR (UL/CSA)
65 kA, 240 V, SCCR (UL/CSA)
65 kA, 480 Y/277 V, SCCR (UL/CSA)
Basic device fixed 15.5 x Iu, Trip Blocks
± 20% tolerance, Trip blocks
Communication
Push-in terminals on output side