Insulated enclosure, flush mounting, for PKZ01 +VHI, +padlocking feature yellow E-PKZ01-SVB-V Eaton Moeller® series E-PKZ0 Insulated enclosure, E-PKZ0, H x W x D = 129 x 90 x 128 mm, flush-mounted, + VHI, + yellow padlock device Motor-protective circuit-breaker enclosure for direct integration into the machine

Automation > Empty enclosure for switchgear
Circuit Breakers PKZ

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Built-in protective housings such as the Eaton Moeller insulated enclosure allow electrical components to be safely integrated directly into panel walls or machinery housings. This configuration saves space while maintaining a high degree of defense against environmental hazards. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Housing material (EF001596): Plastic
  • Width (EF000008): 90 mm
  • Height (EF000040): 129 mm
  • Depth (EF000049): 128 mm
  • With transparent cover (EF001094): No
  • Suitable for emergency stop (EF001433): Yes
  • Model (EF000010): Built-in
  • Degree of protection (IP) (EF005474): IP65

More info

▲

General specifications

Product Name
Eaton Moeller® series E-PKZ0 Accessory Insulated enclosure
Catalog Number
281943
Model Code
E-PKZ01-SVB-V
EAN
4015082819439
Product Length/Depth
128 mm
Product Height
129 mm
Product Width
90 mm
Product Weight
0.264 kg
Certifications
CSA-C22.2 No. 14
CSA Class No.: 3211-05
UL Category Control No.: NLRV
IEC/EN 60947-4-1
UL
CSA File No.: 165628
CSA
CE
UL 508
UL File No.: E36332

Features & Functions

Enclosure material
Plastic
Features
Can be locked in 0 position in combination with VHI-PKZ01
Fitted with:
PE(N) terminal

General

Degree of protection (front side)
IP65
Model
Built-in
Product category
Accessories
Suitable for
Emergency stop

Climatic environmental conditions

Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
40 °C

Design verification

Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
0 A
Static heat dissipation, non-current-dependent Pvs
0 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Please enquire
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Product Datasheet