Type AND CMC, 8 - 32, standard, lockable knob PKE65/AK/XTUW-32-SP Motor-protective circuit-breaker, Type E DOL starters (complete devices), Electronic, 8 - 32 A, Turn button, Screw connection, North America Type E complete device as per UL 508 ((self-protected) combination motor controller), consisting of PKE65 basic device and PKE-XTU-32 trip block, with lockable knob and corresponding extension terminal for UL, can be used for motors with up to 20 horse power (FLA = 27 A / 480 V) or 25 horse power (FLA = 27 A / 600 V), short circuit current rating to UL: 65 kA (480 V/ 277 V) or 25 kA (600 V/ 347 V), electronic wide-range overload protection, high short-circuit breaking capacity to IEC (80 kA / 400 V), can be used as a type F motor starter (combination motor controller) in combination with DILM17 to DILM72 contactors.

Automation > Motor protection circuit-breaker
Electronic Circuit Breakers

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

General specifications

Product Name
Eaton Moeller® series PKE System-protective circuit-breaker
Catalog Number
170483
Model Code
PKE65/AK/XTUW-32-SP
EAN
4015081669813
Product Length/Depth
198 mm
Product Height
204 mm
Product Width
55 mm
Product Weight
1.607 kg
Certifications
CSA-C22.2 No. 14-10
UL60947-4-1A
UL Category Control No.: NKJH
UL
CSA File No.: 012528
IEC/EN 60947-4-1
CSA
CSA Class No.: 3211-08
VDE 0660
CE
UL File No.: E123500
Catalog Notes
This is a product for Environment A (Industrial). In environment B (household) this device may cause undesirable radio interference. In this case the user may be obliged to take appropriate measures.

Features & Functions

Actuator type
Turn button
Functions
Phase failure sensitive
Number of poles
Three-pole

General

Current flow times - min
500 (Class 5) AC-4 cycle operation, Main conducting paths
700 (Class 10) AC-4 cycle operation, Main conducting paths
1000 (Class 20) AC-4 cycle operation, Main conducting paths
For all combinations with an SWD activation, you need not adhere to the minimum current flow times and minimum cut-out periods.
900 (Class 15) AC-4 cycle operation, Main conducting paths
Note: Going below the minimum current flow time can cause overheating of the load (motor).
Cut-out periods - min
≤ 500 ms, main conducting paths, AC-4 cycle operation
Degree of protection
IP20
Overload release current setting - min
8 A
Overload release current setting - max
32 A
Overvoltage category
III
Pollution degree
3
Rated impulse withstand voltage (Uimp)
6000 V AC
Type
Type E DOL starter (complete device)
Resistance per pole
2.2 mΩ

Climatic environmental conditions

Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
55 °C

Electrical rating

Rated operational power at AC-3, 220/230 V, 50 Hz
7.5 kW
Rated operational power at AC-3, 380/400 V, 50 Hz
15 kW
Rated operational voltage (Ue) - min
690 V
Rated operational voltage (Ue) - max
690 V
Rated uninterrupted current (Iu)
32 A

Short-circuit rating

Short-circuit current rating (type E)
65 kA, 480 Y/277 V, SCCR (UL/CSA)
65 kA, 240 V, SCCR (UL/CSA)
25 kA, 600 Y/347 V, SCCR (UL/CSA)
Short-circuit release
448 A, Non-delayed

Motor rating

Assigned motor power at 200/208 V, 60 Hz, 3-phase
7.5 HP
Assigned motor power at 230/240 V, 60 Hz, 3-phase
7.5 HP
Assigned motor power at 460/480 V, 60 Hz, 3-phase
20 HP
Assigned motor power at 575/600 V, 60 Hz, 3-phase
25 HP

Communication

Connection
Screw terminals
Connection to SmartWire-DT
No

Design verification

Equipment heat dissipation, current-dependent Pvid
5.4 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
1.8 W
Rated operational current for specified heat dissipation (In)
32 A
Static heat dissipation, non-current-dependent Pvs
0 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

ETIM for 170483 Low-voltage industrial controls and switchgear (EC000074)
Feature Name Feature Value
Overload release current setting (EF002336) 8 A
Adjustment range undelayed short-circuit release (EF007131) 0 A
With thermal overload protection (EF006233) No
Phase failure sensitive (EF007400) Yes
Switch off technique (EF007007) Electronic
Rated operating voltage (EF001435) 690 V
Rated permanent current Iu (EF001389) 32 A
Rated operation power at AC-3, 230 V (EF007025) 7.5 kW
Rated operation power at AC-3, 400 V (EF001364) 15 kW
Type of electrical connection of main circuit (EF006819) Screw connection
Type of control element (EF006976) Rotating button
Device construction (EF008240) Built-in device fixed built-in technique
With integrated auxiliary switch (EF001387) No
With integrated under voltage release (EF001390) No
Number of poles (EF001391) 3
Rated short-circuit breaking capacity Icu at 400 V, AC (EF007049) 50 kA
Degree of protection (IP) (EF005474) IP20
Height (EF000040) 204 mm
Width (EF000008) 55 mm
Depth (EF000049) 198 mm