View larger
PKE65/AK/XTU-65 158248 Y7-158248 EATON ELECTRIC Motor-Protective Circuit-Breakers, type E CMC 16-65 A, stand..
PKE65/AK/XTU-65
158248
Y7-158248
EATON - MOELLER
1 Pcs.
Automation > Motor protection circuit-breaker
Electronic Circuit Breakers
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The PKE65/AK/XTU-65 158248 Y7-158248 EATON ELECTRIC Motor-Protective Circuit-Breakers, type E CMC 16-65 A, stand.. is designed for controlling and protecting heavy-duty electrical motors. Devices in this category provide electronic tripping characteristics to prevent operational overloads and phase failures in automated systems. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Overload release current setting (EF002336): 16 A
- Adjustment range undelayed short-circuit release (EF007131): 1008 A
- With thermal overload protection (EF006233): No
- Phase failure sensitive (EF007400): Yes
- Switch off technique (EF007007): Electronic
- Rated operating voltage (EF001435): 690 V
- Rated permanent current Iu (EF001389): 65 A
- Rated operation power at AC-3, 230 V (EF007025): 18.5 kW
- Rated operation power at AC-3, 400 V (EF001364): 30 kW
- Type of electrical connection of main circuit (EF006819): Screw connection
- Type of control element (EF006976): Rotating button
- Device construction (EF008240): Built-in device fixed built-in technique
- With integrated auxiliary switch (EF001387): No
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
- Degree of protection (IP) (EF005474): IP20
More info
▲General specifications
UL 60947-4-1
VDE 0660
IEC/EN 60947-4-1
UL
CSA
CE
UL Category Control No.: NLRV
UL File No.: E36332
IEC/EN 60947
CSA Class No.: 3211-05
CSA-C22.2 No. 60947-4-1-14
Features & Functions
Overload release
Motor protection
Phase failure sensitive
General
For all combinations with an SWD activation, you need not adhere to the minimum current flow times and minimum cut-out periods.
Note: Going below the minimum current flow time can cause overheating of the load (motor).
700 (Class 10) AC-4 cycle operation, Main conducting paths
1000 (Class 20) AC-4 cycle operation, Main conducting paths
500 (Class 5) AC-4 cycle operation, Main conducting paths
Terminals: IP00
-5 - 40 °C to IEC/EN 60947, VDE 0660
Ambient conditions, mechanical
Climatic environmental conditions
Damp heat, cyclic, to IEC 60068-2-30
Terminal capacities
1 x (0.75 - 35) mm², ferrule to DIN 46228
2 x (0.75 - 16) mm²
1 Nm, Screw terminals, Control circuit cables
Electrical rating
Short-circuit rating
100 kA, 600 V High Fault, Fuse, SCCR (UL/CSA)
Basic device fixed 15.5 x Iu, Trip Blocks
Trip block fixed 15.5 x Ir
± 20% tolerance, Trip blocks
Switching capacity
58 A, General use UL/CSA