The Eaton Moeller PKE12/AK/XTU-4 158244 Y7-158244 EATON ELECTRIC Motor-protective circuit-breaker, 3p, +control option 1-4A combines electronic trip blocks with standard switching features to protect three-phase electric motors from overcurrents and phase failures. These motor-protective devices are essential for safeguarding automated manufacturing lines. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Overload release current setting (EF002336): 1 A
- Adjustment range undelayed short-circuit release (EF007131): 62 A
- With thermal overload protection (EF006233): No
- Phase failure sensitive (EF007400): Yes
- Switch off technique (EF007007): Electronic
- Rated operating voltage (EF001435): 690 V
- Rated permanent current Iu (EF001389): 4 A
- Rated operation power at AC-3, 230 V (EF007025): 0.75 kW
- Rated operation power at AC-3, 400 V (EF001364): 1.5 kW
- Type of electrical connection of main circuit (EF006819): Screw connection
- Type of control element (EF006976): Rotating button
- Device construction (EF008240): Built-in device fixed built-in technique
- With integrated auxiliary switch (EF001387): No
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
- Degree of protection (IP) (EF005474): IP20
More info
▲General specifications
IEC/EN 60947
CSA File No.: 165628
CE
VDE 0660
UL 60947-4-1
CSA
CSA-C22.2 No. 60947-4-1-14
IEC/EN 60947-4-1
UL Category Control No.: NLRV
UL File No.: E36332
UL
Features & Functions
Motor protection
Overload release
Phase failure sensitive
General
700 (Class 10) AC-4 cycle operation, Main conducting paths
1000 (Class 20) AC-4 cycle operation, Main conducting paths
For all combinations with an SWD activation, you need not adhere to the minimum current flow times and minimum cut-out periods.
Note: Going below the minimum current flow time can cause overheating of the load (motor).
900 (Class 15) AC-4 cycle operation, Main conducting paths
IP20
-25 - 55 °C, Operating range
Ambient conditions, mechanical
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Terminal capacities
1 x (1 - 6) mm², ferrule to DIN 46228
2 x (1 - 6) mm²
1.7 Nm, Screw terminals, Main cable
Electrical rating
Short-circuit rating
100 A, Class J, 600 V High Fault, max. Fuse, SCCR (UL/CSA)
Delayed approx. 60 ms, Trip blocks
± 20% tolerance, Trip blocks
Basic device fixed 15.5 x Iu, Trip Blocks