View larger
PKE-XTUACP-36 168795 Y7-168795 EATON ELECTRIC Trip block, 3p, 15-36A, system protection, advanced
PKE-XTUACP-36
168795
Y7-168795
EATON - MOELLER
1 Pcs.
Automation > Tripping bloc for power circuit-breaker
Electronic Circuit Breakers
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller PKE-XTUACP-36 168795 Y7-168795 trip block provides advanced system protection for industrial electrical distribution networks and motor circuits. These modular components attach directly to switchgear to deliver precise electronic monitoring and timely interruption during abnormal current fluctuations.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Type of motor protection (EF008234): Electronic release
- Number of poles (EF001391): 3
- Rated permanent current Iu (EF001389): 36 A
- Overload release current setting (EF002336): 15 A
- Short-circuit release function (EF001413): Delayed
- With ground fault protection function (EF005601): No
- External power supply required (EF003292): No
- Width (EF000008): 45 mm
- Height (EF000040): 64.2 mm
- Depth (EF000049): 41.6 mm
More info
▲General specifications
VDE 0660
Features & Functions
System protection
Short-circuit protection
Line and cable protection
General
For all combinations with an SWD activation, you need not adhere to the minimum current flow times and minimum cut-out periods.
900 (Class 15) AC-4 cycle operation, Main conducting paths
1000 (Class 20) AC-4 cycle operation, Main conducting paths
Note: Going below the minimum current flow time can cause overheating of the load (motor).
700 (Class 10) AC-4 cycle operation, Main conducting paths
Device: IP20
-5 - 40 °C to IEC/EN 60947, VDE 0660
Ambient conditions, mechanical
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Electrical rating
Short-circuit rating
Delayed approx. 60 ms, Trip blocks
75 A - 288 A, Irm, Setting range
± 20% tolerance, Trip blocks
Magnet system
Communication
In conjunction with PKE-SWD-SP SmartWire DT PKE module