EATON - MOELLER PKDM-2/1N/D/03-A PKDM-2/1N/D/03-A 248782 EATON ELECTRIC RCD/MCB, 2A, 300mA, miniature circuit-breaker trip curve D, 1pole+N, .. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

PKDM-2/1N/D/03-A 248782 EATON ELECTRIC RCD/MCB, 2A, 300mA, miniature circuit-breaker trip curve D, 1pole+N, ..

PKDM-2/1N/D/03-A

248782

EATON - MOELLER

1 Pcs.

RCD/MCB, 2A, 300mA, miniature circuit-breaker trip curve D, 1pole+N, residual current circuit-breaker trip characteristic: A Int. Combined, 2A, 300mA, D curve, 1P+N, class A RCBO (residual-current circuit breaker with overload protection) PKDM, 1 pole+N, Tripping characteristic: D, Rated current In: 2 A, Rated switching capacity according to IEC/EN 61009: 10 kA, Rated fault current IΔN: 0.3 A, Pulse-current sensitive, Partly surge-proof 250 A, Switchgear for residential and commercial applications

Automation > Earth leakage circuit breaker
Modular Switchgear – Tertiary and Differential

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

An Eaton Moeller PKDM-2/1N/D/03-A RCD/MCB unit integrates overload protection and residual current monitoring to secure electrical circuits against various fault conditions. These devices are widely installed in industrial panels where sensitive automation equipment requires reliable line protection. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Number of poles (total): 2
  • Number of protected poles: 1
  • Rated current: 2 A
  • Rated fault current: 0.3 A
  • Leakage current type: A
  • Current limiting class: 3
  • Surge current capacity: 0.25 kA
  • Voltage type: AC
  • Frequency: 50 Hz
  • Release characteristic: D
  • Concurrently switching neutral conductor: Yes
  • With interlocking device: No
  • Over voltage category: 3
  • Pollution degree: 2
  • Width in number of modular spacings: 2
  • Built-in depth: 69.5 mm

More info

▲
RCD/MCB, 2A, 300mA, miniature circuit-breaker trip curve D, 1pole+N, residual current circuit-breaker trip characteristic: A
RCBO (residual-current circuit breaker with overload protection) PKDM, 1 pole+N, Tripping characteristic: D, Rated current In: 2 A, Rated switching capacity according to IEC/EN 61009: 10 kA, Rated fault current IΔN: 0.3 A, Pulse-current sensitive, Partly surge-proof 250 A, Switchgear for residential and commercial applications

Delivery program

Basic function
Combined RCD/MCB devices
Number of poles
1 pole+N
Tripping characteristic
D
Application
Switchgear for residential and commercial applications
Rated current [In]
2 A
Rated switching capacity according to IEC/EN 61009
10 kA
Rated fault current [IΔN]
0.3 A
Type
Type A
Tripping
non-delayed s…
Product range
PKDM
Sensitivity
Pulse-current sensitive
Impulse withstand current
Partly surge-proof 250 A

Technical data

Electrical
Sensitivity
Pulse-current sensitive

Design verification as per IEC/EN 61439

Rated operational current for specified heat dissipation [In]
2 A
Heat dissipation per pole, current-dependent [Pvid]
0 W
Equipment heat dissipation, current-dependent [Pvid]
1.4 W
Static heat dissipation, non-current-dependent [Pvs]
0 W
Heat dissipation capacity [Pdiss]
0 W
Operating ambient temperature min.
-25 °C
Operating ambient temperature max.
+40 °C

Technical data ETIM 7.0

Circuit breakers and fuses (EG000020) / Earth leakage circuit breaker (EC000905)
Electric engineering, automation, process control engineering / Electrical installation, device / Residual current protection system / MCB/RCCB combination ([email protected] [AFZ810015])
Number of poles (total)
2
Number of protected poles
1
Rated voltage
230 V
Rated insulation voltage Ui
V
Rated impulse withstand voltage Uimp
kV
Rated current
2 A
Rated fault current
0.3 A
Leakage current type
A
Current limiting class
3
Rated short-circuit breaking capacity acc. EN 61009
kA
Rated short-circuit breaking capacity IEC 60947-2
0 kA
Rated short-circuit breaking capacity Icn acc. EN 61009-1
kA
Disconnection characteristic
Surge current capacity
0.25 kA
Voltage type
AC
Frequency
50 Hz
Release characteristic
D
Concurrently switching N-neutral
Yes
With interlocking device
Over voltage category
3
Pollution degree
2
Ambient temperature during operating
°C
Width in number of modular spacings
2
Built-in depth
69.5 mm
Suitable for flush-mounted installation
No
Anti-nuisance tripping version
No
Degree of protection (IP)
IP20
Connectable conductor cross section solid-core
mm²
Connectable conductor cross section multi-wired
mm²

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.