EATON - MOELLER PKDM-16/1N/B/03-A PKDM-16/1N/B/03-A 248777 EATON ELECTRIC RCD/MCB, 16A, 300mA, miniature circuit-breaker trip curve B, 1pole+N.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

PKDM-16/1N/B/03-A 248777 EATON ELECTRIC RCD/MCB, 16A, 300mA, miniature circuit-breaker trip curve B, 1pole+N..

PKDM-16/1N/B/03-A

248777

EATON - MOELLER

1 Pcs.

RCD/MCB, 16A, 300mA, miniature circuit-breaker trip curve B, 1pole+N, residual current circuit-breaker trip characteristic: A Int. Combined, 16A, 300mA, B-curve, 1P+N, Class A RCBO (residual-current circuit breaker with overload protection) PKDM, 1 pole+N, Tripping characteristic: B, Rated current In: 16 A, Rated switching capacity according to IEC/EN 61009: 10 kA, Rated fault current IΔN: 0.3 A, Pulse-current sensitive, Partly surge-proof 250 A, Switchgear for residential and commercial applications

Automation > Earth leakage circuit breaker
Modular Switchgear – Tertiary and Differential

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

The Eaton Moeller PKDM-16/1N/B/03-A is an RCD/MCB combination module configured to protect electrical circuits against thermal overloads, short circuits, and earth leakage currents. It provides dual-layer defense for industrial control panels and automation setups. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Number of poles (total) (EF008618): 2
  • Number of protected poles (EF005548): 1
  • Rated current (EF000227): 16 A
  • Rated fault current (EF002358): 0.3 A
  • Leakage current type (EF002560): A
  • Current limiting class (EF002568): 3
  • Surge current capacity (EF002564): 0.25 kA
  • Voltage type (EF000187): AC
  • Frequency (EF005455): 50 Hz
  • Release characteristic (EF000889): B
  • Concurrently switching neutral conductor (EF005997): Yes
  • With interlocking device (EF007385): No
  • Over voltage category (EF002569): 3
  • Pollution degree (EF002570): 2
  • Width in number of modular spacings (EF002950): 2
  • Built-in depth (EF000218): 69.5 mm

More info

General specifications

Product Name
Eaton Moeller series RCBO - Residual-current circuit breaker with overcurrent protection
Catalog Number
248777
Model Code
PKDM-16/1N/B/03-A
EAN
4015082487775
Product Length/Depth
80 mm
Product Height
60 mm
Product Width
35 mm
Product Weight
0.225 kg
Compliances
CE Marked
Certifications
CE

Product specifications

Type
RCBO
Voltage rating
230 V
Surge current capacity
0.25 kA
Voltage type
AC
Width in number of modular spacings
2
Features
Concurrently switching N-neutral
Product range
PKDM
Rated current
16 A
Rated operational current for specified heat dissipation (In)
16 A
Rated switching capacity (IEC/EN 61009)
10 kA
Static heat dissipation, non-current-dependent
0 W
Tripping characteristic
B
Built-in depth
69.5 mm
Current limiting class
3
Rated short-circuit breaking capacity (EN 60947-2)
0 kA
Fault current rating
0.3 A
Heat dissipation capacity
0 W
Heat dissipation per pole, current-dependent
0 W
Number of poles (protected)
1
Number of poles (total)
2
Rated switching capacity
10 kA
Basic function
Combined RCD/MCB devices
Equipment heat dissipation, current-dependent
3.6 W
Degree of protection
IP20
Tripping
Non-delayed
Overvoltage category
III
Pollution degree
2
Impulse withstand current
Partly surge-proof, 250 A
Leakage current type
A
Release characteristic
B
Sensitivity type
Type A, pulse-current sensitive
Frequency rating
50 Hz
Number of poles
Single-pole + N

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.