Used with
The reference values indicated in the table apply to the basic elements of the distribution board. As far as devices, terminals etc. fitted into the enclosures are concerned, their own specific technical data and rated values apply.
Special features
Low-voltage fuses (IEC/EN 60269, VDE 0636)Sealable cover fastenersSides closed, but with full area knockoutOpen topFitting of cable supports in the distribution board with wedge-lock fastenerGland plate can be split, cables can be inserted from the front
Type
Basic enclosurePanel enclosure with gland plates fittedxEnergy Safety Ci
Features
UV resistance beneath protective shield
Cover with overpressure release
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
Meets the product standard's requirements.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Lower part: 960 °C / cover: 850 °C
10.2.4 Resistance to ultra-violet (UV) radiation
Not relevant to indoor installations.
10.2.5 Lifting
20 kg per enclosure with support frame and lifting aid met; assembled and secured as per the latest applicable instruction leaflet.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
10.4 Clearances and creepage distances
Is the panel builder's responsibility.
10.5 Protection against electric shock
Protection class 2, therefore not applicable.
10.6 Incorporation of switching devices and components
Is the panel builder's responsibility.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
10.9.3 Impulse withstand voltage
10.9.4 Testing of enclosures made of insulating material
Meets the product standard's requirements.
Creepage resistance
KB160, KC175 (base, to IEC 60112)
KB100, KC200 (cover, to IEC 60112)
Degree of protection
IP65 (enclosure)
IP64 (KST cable entries from above)
IP00 (cable entry open)
IP65 (KST cable entries from below)
IP65
IK10
Other
Chemical resistance
Partly resistant to: Acids > 10 %
Not resistant to: alkalis, benzene
Resistant against: acids < 10 %, mineral oil, alcohol, gasoline, greases, salt solutions
Ambient operating temperature - max
Ambient operating temperature - min
Heat diss. ambient 35°C delta T:20°C wall mount individ. encl. top (IEC 60890)
Heat diss. ambient 35°C delta T: 20°C wall mount middle encl. top (IEC 60890)
Heat diss. ambient 35°C delta T:20°C wall mount starting encl. top (IEC 60890)
Heat diss. ambient 35°C delta T:35°C wall mount individ. encl. top (IEC 60890)
Heat diss. ambient 35°C delta T: 35°C wall mount middle encl. top (IEC 60890)
Heat diss. ambient 35°C delta T:35°C wall mount starting encl. top (IEC 60890)
Color
Gray
Light gray (RAL 7035, base)
Transparent, smoky gray (cover)
Number of openings (flange plates)
Operating altitude without derating - max
Plate thickness (cabinet)
Plate thickness (cover/door)
Surface resistance (IEC 60093)
Width in number of modular spacings
Material
Halogen free
Glass-fibre reinforced polycarbonate (base)
Non-reinforced polycarbonate (cover)
Mounting method
Surface mounted (plaster)
Creepage and clearance distances
III/3 to IEC/EN 60439-1 (standard)
Temperature resistance
Temperature resistant: -40 °C - 120 °C (enclosure)
Temperature resistant: 85 °C (enclosure bolt)
Temperature resistant: 80 °C (gasket)
Flammability characteristics (UL)
V2 (cover) (UL94)
V1 (base) (UL94)
Flammability characteristics of glow rod test
VDE 0304 Part 3 level IIb, level IIb to IEC 60707
Relative humidity
50 % (at 40 °C)
90 % (at 20 °C)
Mean ambient operating temperature (24 hours)
Mounting depth with mounting plate
Suitable for
Lightning protection
Outdoor use