View larger
FAZ-C0,5/1-NA 102077 Y7-102077 EATON ELECTRIC Miniature circuit breaker (MCB), 0,5A, 1p, C-Char, AC
FAZ-C0,5/1-NA
102077
Y7-102077
EATON - MOELLER
1 Pcs.
Automation > Miniature circuit breaker (MCB)
Modular Switchgear – Industrial
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Manufactured by Eaton Moeller, the FAZ-C0,5/1-NA is a miniature circuit breaker (MCB) built to offer precise overcurrent protection for low-amperage electrical control circuits. Low-rating protective devices are essential in automation panels to safeguard sensitive instrumentation and control wiring against minor fault currents. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Built-in depth (EF000218): 70.5 mm
- Release characteristic (EF000889): C
- Number of poles (total) (EF008618): 1
- Number of protected poles (EF005548): 1
- Rated current (EF000227): 0.5 A
- Rated voltage (EF000228): 240 V
- Rated insulation voltage Ui (EF001366): 440 V
- Rated impulse withstand voltage Uimp (EF011980): 4 kV
- Voltage type (EF000187): AC
- Frequency (EF000416): 50 Hz
- Current limiting class (EF002568): 3
- Flush-mounted installation (EF007517): No
- Concurrently switching neutral conductor (EF005997): No
- Over voltage category (EF002569): 3
- Pollution degree (EF002570): 2
- Additional equipment possible (EF008148): Yes
More info
▲General specifications
CSA (Class No. 1432-01)
IEC 60947-2
UL (File No. E235139)
UL 489
Specially designed for North America, suitable as BCPD
North America (UL listed, CSA certified)
CE marking
CSA-C22.2 No. 5-09
IEC/EN 60947-2
CSA (File No. 204453)
UL 489, CSA C22.2 No. 5
EN45545-2
IEC 61373
Delivery program
- FAZ-NA
- Miniature circuit breaker
Technical data - electrical
Technical data - mechanical
IP20 (IEC)
IP20
IP40 (when fitted)
Max. 2.4 Nm
UL: 2.8 Nm (25 lb-in) for AWG 10 - AWG 8
UL: 2.4 Nm (21 lb-in) for AWG 18 - AWG 12
Design verification as per IEC/EN - technical data
Additional information
Miniature circuit breaker