EATON - MOELLER PLN6-C25/1N-MW PLN6-C25/1N-MW 263176 EATON ELECTRIC Over current switch, 25A, 1Np, C-Char, AC View larger
Images are for illustrative purposes only. Please refer to data sheet for details

PLN6-C25/1N-MW 263176 EATON ELECTRIC Over current switch, 25A, 1Np, C-Char, AC

PLN6-C25/1N-MW

263176

EATON - MOELLER

1 Pcs.

Over current switch, 25A, 1Np, C-Char, AC Miniature circuit breaker (MCB), PLN6, 1-pole+N, tripping characteristic: C, rated current In: 25 A, rated switching capacity according to IEC/EN 60898-1: 6 kA, Switchgear for residential and commercial applications

Automation > Miniature circuit breaker (MCB)
Modular Switchgear - Tertiary

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

General specifications

Product Name
Eaton Moeller series xPole - PLN6 MCB
Catalog Number
263176
Model Code
PLN6-C25/1N-MW
EAN
4015082631765
Product Length/Depth
80 mm
Product Height
75 mm
Product Width
17.5 mm
Product Weight
0.122 kg
Compliances
RoHS conform

Delivery program

Application
Number of poles
Single-pole + N
Number of poles (total)
2
Number of poles (protected)
1
Tripping characteristic
C
Release characteristic
C
Amperage Rating
25 A
Type
  • Miniature circuit breaker
  • PLN6

Technical data - electrical

Voltage type
AC
Rated operational voltage (Ue) - max
230 V
Rated insulation voltage (Ui)
440 V
Rated impulse withstand voltage (Uimp)
4 kV
Frequency rating - min
50 Hz
Frequency rating - max
60 Hz
Rated switching capacity (IEC/EN 60898-1)
6 kA
Rated short-circuit breaking capacity (EN 60898) at 230 V
6 kA
Rated short-circuit breaking capacity (EN 60898) at 400 V
6 kA
Rated short-circuit breaking capacity (IEC 60947-2) at 230 V
0 kA
Rated short-circuit breaking capacity (IEC 60947-2) at 400 V
0 kA
Overvoltage category
III
Pollution degree
2

Technical data - mechanical

Width in number of modular spacings
1
Built-in depth
60 mm
Degree of protection
IP20
Connectable conductor cross section (solid-core) - min
1 mm²
Connectable conductor cross section (solid-core) - max
16 mm²
Connectable conductor cross section (multi-wired) - min
1 mm²
Connectable conductor cross section (multi-wired) - max
16 mm²

Design verification as per IEC/EN 61439 - technical data

Rated operational current for specified heat dissipation (In)
25 A
Heat dissipation per pole, current-dependent
0 W
Equipment heat dissipation, current-dependent
3.2 W
Static heat dissipation, non-current-dependent
0 W
Heat dissipation capacity
0 W
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
75 °C

Additional information

Current limiting class
3
Features
Additional equipment possible
Concurrently switching N-neutral
Special features
Ambient temperature hint: Starting at 55 °C a 1 °C increase results in a 0.5% linear reduction of current carrying capacity
Used with
Miniature circuit breaker
PLN6

ETIM for 263176 Circuit breakers and fuses (EC000042)
Feature Name Feature Value
Built-in depth (EF000218) 60 mm
Release characteristic (EF000889) C
Number of poles (total) (EF008618) 2
Number of protected poles (EF005548) 1
Rated current (EF000227) 25 A
Rated voltage (EF000228) 230 V
Rated insulation voltage Ui (EF001366) 440 V
Rated impulse withstand voltage Uimp (EF011980) 4 kV
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V (EF009556) 6 kA
Voltage type (EF000187) AC
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V (EF009555) 6 kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V (EF009557) 0 kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V (EF009558) 0 kA
Frequency (EF000416) 50 Hz
Power loss (EF005387) 4.1 W
Current limiting class (EF002568) 3
Flush-mounted installation (EF007517) No
Concurrently switching neutral conductor (EF005997) Yes
Over voltage category (EF002569) 3
Pollution degree (EF002570) 2
Additional equipment possible (EF008148) Yes
Width in number of modular spacings (EF002950) 1
Degree of protection (IP) (EF005474) IP20
Ambient temperature during operating (EF007515) -25 °C
Connectable conductor cross section multi-wired (EF007343) 1 mm²
Connectable conductor cross section solid-core (EF007337) 1 mm²
Explosion-proof (EF004663) No

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.