EATON - MOELLER NZMS2-4-A160/100-SVE NZMS2-4-A160/100-SVE 113315 Y7-113315 EATON ELECTRIC NZMS2-4-A160/100-SVE View larger
Images are for illustrative purposes only. Please refer to data sheet for details

NZMS2-4-A160/100-SVE 113315 Y7-113315 EATON ELECTRIC NZMS2-4-A160/100-SVE

NZMS2-4-A160/100-SVE

113315

Y7-113315

EATON - MOELLER

1 Pcs.

NZMS2-4-A160/100-SVE NZMS2-4-A160/100-SVE. Circuit breaker 4-pole 160A, system/cable protection, withdrawable unit Series NZM..-A circuit-breakers cover all application cases with just four compact sizes and are suitable for the IEC market. Modular function groups always make mounting flexible. With thermomagnetic releases for systems and cable protection. Notes: set value in neutral conductor is synchronous with set value Ir of phase conductor.

Automation > Power circuit-breaker for trafo/generator/installation protection
Circuit Breakers NZM

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

A circuit-breaker like the Eaton Moeller NZMS2-4-A160/100-SVE provides essential overcurrent protection for commercial and industrial electrical installations. These components automatically interrupt fault currents to prevent equipment damage and maintain operational safety.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Rated permanent current Iu (EF001389): 160 A
  • Rated voltage (EF003977): 690 V
  • Overload release current setting (EF002336): 125 A
  • Adjustment range undelayed short-circuit release (EF007131): 6 A
  • Device construction (EF008240): Built-in device plug-in technique
  • Integrated earth fault protection (EF007296): No
  • Type of electrical connection of main circuit (EF006819): Screw connection
  • Suitable for DIN rail (top hat rail) mounting (EF007250): No
  • DIN rail (top hat rail) mounting optional (EF008904): No
  • With switched-off indicator (EF007006): No
  • With integrated under voltage release (EF001390): No
  • Number of poles (EF001391): 4
  • Position of connection for main current circuit (EF006671): Back
  • Type of control element (EF006976): Rocker lever
  • Complete device with protection unit (EF008906): Yes
  • Motor drive integrated (EF006697): No

More info

▲

General Specifications

Product Name
Eaton Moeller series NZM molded case circuit breaker thermo-magnetic
Catalog Number
113315
Ean
4015081128501
Product Length/Depth
180 mm
Product Height
245 mm
Product Width
140 mm
Product Weight
4.07 kg
Compliances
RoHS conform
Model Code
NZMS2-4-A160/100-SVE

Technical Data - Electrical

Voltage rating
690 V - 690 V
Current rating of neutral conductor
60% of phase conductor
Amperage Rating
160 A
Instantaneous current setting (Ii) - min
6 A
Instantaneous current setting (Ii) - max
10 A
Overload current setting (Ir)
80 A - 100 A
Overload current setting (Ir) - min
125 A
Overload current setting (Ir) - max
160 A
Short delay current setting (Isd) - min
0 A
Short delay current setting (Isd) - max
0 A
Short-circuit release non-delayed setting - min
6 A
Short-circuit release non-delayed setting - max
10 A
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz
70 kA
Electrical connection type of main circuit
Screw connection
Handle type
Rocker lever
Overvoltage category
Iii
Pollution degree
3

Technical data - communication

Current rating of neutral conductor
60% of phase conductor
Amperage Rating
160 A
Instantaneous current setting (Ii) - min
6 A
Instantaneous current setting (Ii) - max
10 A
Overload current setting (Ir)
80 A - 100 A
Overload current setting (Ir) - min
125 A
Overload current setting (Ir) - max
160 A
Short delay current setting (Isd) - min
0 A
Short delay current setting (Isd) - max
0 A
Short-circuit release non-delayed setting - min
6 A
Short-circuit release non-delayed setting - max
10 A
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz
70 kA
Electrical connection type of main circuit
Screw connection
Handle type
Rocker lever
Overvoltage category
Iii
Pollution degree
3

Technical data - mechanical

Mounting Method
Built-in device plug-in technique
Degree of protection
IP20
Number of auxiliary contacts (change-over contacts)
0
Number of auxiliary contacts (normally closed contacts)
0
Number of auxiliary contacts (normally open contacts)
0
Position of connection for main current circuit
Back side

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.