EATON - MOELLER NZMN2-PMX200-NA NZMN2-PMX200-NA 192582 EATON ELECTRIC Automatic int. NZM2 PXR25, 200A, 3p, screw terminal, UL/CSA View larger
Images are for illustrative purposes only. Please refer to data sheet for details

NZMN2-PMX200-NA 192582 EATON ELECTRIC Automatic int. NZM2 PXR25, 200A, 3p, screw terminal, UL/CSA

NZMN2-PMX200-NA

192582

Y7-192582

EATON - MOELLER

1 Pcs.

Automatic int. NZM2 PXR25, 200A, 3p, screw terminal, UL/CSA The xEffect NZM...-PMX-NA circuit breaker range with power expert release (PXR) electronic triggering system covers use cases for motor protection with only four compact sizes and is suitable for the IEC market. The integrated energy measuring function supplies currents, voltages and active energy (kWh) with accuracy class 1 according to IEC 61557-12. Test function and settings via micro USB port directly on the switch. Modular function groups always make mounting flexible and may be supplemented by the comprehensive range of accessories. R.m.s. value measurement and thermal memory.

Automation > Motor protection circuit-breaker
Circuit Breakers NZM

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

NZMN2-PMX200-NA 192582 EATON ELECTRIC Automatic int. NZM2 PXR25, 200A, 3p, screw terminal, UL/CSA supplied by Eaton Moeller is an automatic circuit breaker designed to provide advanced electronic protection for North American electrical distribution systems. Units of this type protect distribution feeders and heavy loads from current irregularities.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Overload release current setting (EF002336): 88 A
  • Adjustment range undelayed short-circuit release (EF007131): 400 A
  • With thermal overload protection (EF006233): Yes
  • Phase failure sensitive (EF007400): Yes
  • Switch off technique (EF007007): Electronic
  • Rated operating voltage (EF001435): 690 V
  • Rated operation power at AC-3, 230 V (EF007025): 55 kW
  • Rated operation power at AC-3, 400 V (EF001364): 110 kW
  • Type of electrical connection of main circuit (EF006819): Screw connection
  • Type of control element (EF006976): Rocker lever
  • Device construction (EF008240): Built-in device fixed built-in technique
  • With integrated auxiliary switch (EF001387): No
  • With integrated under voltage release (EF001390): No
  • Number of poles (EF001391): 3
  • Degree of protection (IP) (EF005474): IP20
  • Height (EF000040): 195 mm

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.