EATON - MOELLER NZMH4-PX1000-NA NZMH4-PX1000-NA 192596 EATON ELECTRIC Automatic Int. NZM4 PXR25, 1000A, 3p, Screw Terminal, UL/CSA View larger
Images are for illustrative purposes only. Please refer to data sheet for details

NZMH4-PX1000-NA 192596 EATON ELECTRIC Automatic Int. NZM4 PXR25, 1000A, 3p, Screw Terminal, UL/CSA

NZMH4-PX1000-NA

192596

Y7-192596

EATON - MOELLER

1 Pcs.

Automatic Int. NZM4 PXR25, 1000A, 3p, Screw Terminal, UL/CSA The xEffect NZM...-PX-NA circuit breaker range with power expert release (PXR) electronic triggering system covers use cases for full range protection with only four compact sizes and is suitable for the IEC and UL/CSA market. The integrated energy measuring function supplies currents, voltages and active energy (kWh) with accuracy class 1 according to IEC 61557-12. Test function and settings via micro USB port directly on the switch. Modular function groups always make mounting flexible and may be supplemented by the comprehensive range of accessories. R.m.s. value measurement and thermal memory.

Automation > Power circuit-breaker for trafo/generator/installation protection
Circuit Breakers NZM

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

General Specifications

Product Name
Eaton Moeller series NZM molded case circuit breaker electronic
Catalog Number
192596
Ean
4015081933242
Product Length/Depth
401 mm
Product Height
207 mm
Product Width
210 mm
Product Weight
21 kg
Compliances
RoHS conform
Certifications
Specially designed for North America
UL listed
CSA-C22.2 No. 5-09
CSA certified
UL (Category Control Number DIVQ)
UL (File No. E31593)
IEC 60947-2
CSA (File No. 22086)
UL/CSA
IEC
CSA (Class No. 1432-01)
IEC/EN 60947
UL 489
CE marking
Model Code
NZMH4-PX1000-NA

Technical Data - Electrical

Voltage rating
690 V - 690 V
Rated operating voltage Ue (UL) - max
600 V
Rated impulse withstand voltage (Uimp) at auxiliary contacts
6000 V
Rated impulse withstand voltage (Uimp) at main contacts
8000 V
Rated operational current
1600 A (660-690 V AC-3, making and breaking capacity)
1600 A (415 V AC-1, making and breaking capacity)
2000 A (690 V AC -1, making and breaking capacity)
2000 A (380/400 V AC-1, making and breaking capacity)
Rated short-time withstand current (t = 0.3 s)
19.2 kA
Rated short-time withstand current (t = 1 s)
19.2 kA
Amperage Rating
1000 A
Instantaneous current setting (Ii) - min
2 A
Instantaneous current setting (Ii) - max
18 A
Overload current setting (Ir) - min
400 A
Overload current setting (Ir) - max
1000 A
Short delay current setting (Isd) - min
2000 A
Short delay current setting (Isd) - max
10000 A
Short-circuit release delayed setting - min
800 A
Short-circuit release delayed setting - max
10000 A
Short-circuit release non-delayed setting - min
2000 A
Short-circuit release non-delayed setting - max
18000 A
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 230 V, 50/60 Hz
63 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz
50 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 440 V, 50/60 Hz
50 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 525 V, 50/60 Hz
50 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 690 V, 50/60 Hz
37 kA
Rated short-circuit making capacity Icm at 240 V, 50/60 Hz
275 kA
Rated short-circuit making capacity Icm at 400/415 V, 50/60 Hz
187 kA
Rated short-circuit making capacity Icm at 440 V, 50/60 Hz
187 kA
Rated short-circuit making capacity Icm at 525 V, 50/60 Hz
143 kA
Rated short-circuit making capacity Icm at 690 V, 50/60 Hz
100 kA
Short-circuit total breaktime
< 25 ms (≦ 415 V); < 35 ms (> 415 V)
Electrical connection type of main circuit
Screw connection
Isolation
500 V AC (between auxiliary contacts and main contacts)
300 V AC (between the auxiliary contacts)
Number of operations per hour - max
60
Handle type
Rocker lever
Utilization category
B (2000A: A, IEC/EN 60947-2)
Overvoltage category
Iii
Pollution degree
3
Lifespan, electrical
2000 operations at 415 V AC-3
2000 operations at 400 V AC-3
3000 operations at 400 V AC-1
2000 operations at 690 V AC-1
1000 operations at 690 V AC-3
Direction of incoming supply
As required

Technical data - communication

Rated impulse withstand voltage (Uimp) at auxiliary contacts
6000 V
Rated impulse withstand voltage (Uimp) at main contacts
8000 V
Rated operational current
1600 A (660-690 V AC-3, making and breaking capacity)
1600 A (415 V AC-1, making and breaking capacity)
2000 A (690 V AC -1, making and breaking capacity)
2000 A (380/400 V AC-1, making and breaking capacity)
Rated short-time withstand current (t = 0.3 s)
19.2 kA
Rated short-time withstand current (t = 1 s)
19.2 kA
Amperage Rating
1000 A
Instantaneous current setting (Ii) - min
2 A
Instantaneous current setting (Ii) - max
18 A
Overload current setting (Ir) - min
400 A
Overload current setting (Ir) - max
1000 A
Short delay current setting (Isd) - min
2000 A
Short delay current setting (Isd) - max
10000 A
Short-circuit release delayed setting - min
800 A
Short-circuit release delayed setting - max
10000 A
Short-circuit release non-delayed setting - min
2000 A
Short-circuit release non-delayed setting - max
18000 A
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 230 V, 50/60 Hz
63 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz
50 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 440 V, 50/60 Hz
50 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 525 V, 50/60 Hz
50 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 690 V, 50/60 Hz
37 kA
Rated short-circuit making capacity Icm at 240 V, 50/60 Hz
275 kA
Rated short-circuit making capacity Icm at 400/415 V, 50/60 Hz
187 kA
Rated short-circuit making capacity Icm at 440 V, 50/60 Hz
187 kA
Rated short-circuit making capacity Icm at 525 V, 50/60 Hz
143 kA
Rated short-circuit making capacity Icm at 690 V, 50/60 Hz
100 kA
Short-circuit total breaktime
< 25 ms (≦ 415 V); < 35 ms (> 415 V)
Electrical connection type of main circuit
Screw connection
Isolation
500 V AC (between auxiliary contacts and main contacts)
300 V AC (between the auxiliary contacts)
Number of operations per hour - max
60
Handle type
Rocker lever
Utilization category
B (2000A: A, IEC/EN 60947-2)
Overvoltage category
Iii
Pollution degree
3
Lifespan, electrical
2000 operations at 415 V AC-3
2000 operations at 400 V AC-3
3000 operations at 400 V AC-1
2000 operations at 690 V AC-1
1000 operations at 690 V AC-3
Direction of incoming supply
As required

Technical data - mechanical

Mounting Method
Built-in device fixed built-in technique
Fixed
Degree of protection
IP20 (basic degree of protection, in the operating controls area)
IP20
Degree of protection (IP), front side
IP40 (with insulating surround)
IP66 (with door coupling rotary handle)
Degree of protection (terminations)
IP10 (tunnel terminal)
IP00 (terminations, phase isolator and strip terminal)
Protection against direct contact
Finger and back-of-hand proof to DIN EN 50274/VDE 0106 part 110
Shock resistance
15 g (half-sinusoidal shock 11 ms)
Number of auxiliary contacts (change-over contacts)
0
Number of auxiliary contacts (normally closed contacts)
0
Number of auxiliary contacts (normally open contacts)
0
Position of connection for main current circuit
Front side
Climatic proofing
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78
Lifespan, mechanical
10000 operations

ETIM for 192596 Low-voltage industrial controls and switchgear (EC000228)
Feature Name Feature Value
Rated permanent current Iu (EF001389) 1000 A
Rated voltage (EF003977) 690 V
Rated short-circuit breaking capacity Icu at 400 V, 50 Hz (EF007048) 50 kA
Overload release current setting (EF002336) 400 A
Adjustment range short-term delayed short-circuit release (EF007129) 2000 A
Adjustment range undelayed short-circuit release (EF007131) 2 A
Device construction (EF008240) Built-in device fixed built-in technique
Integrated earth fault protection (EF007296) No
Type of electrical connection of main circuit (EF006819) Screw connection
Suitable for DIN rail (top hat rail) mounting (EF007250) No
DIN rail (top hat rail) mounting optional (EF008904) No
Number of auxiliary contacts as normally closed contact (EF001377) 0
Number of auxiliary contacts as normally open contact (EF001376) 0
Number of auxiliary contacts as change-over contact (EF003531) 0
With switched-off indicator (EF007006) No
With integrated under voltage release (EF001390) No
Number of poles (EF001391) 3
Position of connection for main current circuit (EF006671) Front
Type of control element (EF006976) Rocker lever
Complete device with protection unit (EF008906) Yes
Motor drive integrated (EF006697) No
Motor drive optional (EF007386) Yes
Degree of protection (IP) (EF005474) IP20

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.