Request QuoteProduct Overview
An Eaton Moeller NZMH3-PMX250-SVE circuit breaker provides heavy-duty power distribution protection and short-circuit isolation for high-capacity industrial electrical networks. Built-in mechanisms handle fault current interruption and safeguard downstream machinery effectively.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Overload release current setting (EF002336): 100 A
- Adjustment range undelayed short-circuit release (EF007131): 2 A
- With thermal overload protection (EF006233): Yes
- Phase failure sensitive (EF007400): Yes
- Switch off technique (EF007007): Electronic
- Rated operating voltage (EF001435): 690 V
- Rated permanent current Iu (EF001389): 250 A
- Rated operation power at AC-3, 230 V (EF007025): 75 kW
- Rated operation power at AC-3, 400 V (EF001364): 132 kW
- Type of control element (EF006976): Rocker lever
- Device construction (EF008240): Built-in device plug-in technique
- With integrated auxiliary switch (EF001387): No
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
- Degree of protection (IP) (EF005474): IP20
- Height (EF000040): 215.2 mm
More info
▲IEC
The circuit-breaker fulfills all requirements for AC-3 switching category.
R.m.s. value measurement and “thermal memory”
Adjustable time delay setting to overcome current peaks tr at 6 x Ir also infinity (without overload releases)
All AC-3 rating data applies to direct switching by the circuit-breaker under normal operating conditions. If, for example, a contactor takes over AC-3 switching under normal operating conditions, the full rated uninterrupted current applies to the circuit-breaker, In = Iu.
Maximum back-up fuse, if the expected short-circuit currents at the installation location exceed the switching capacity of the circuit breaker (Rated short-circuit breaking capacity Icn)
Rated current = rated uninterrupted current: 250 A
Terminal capacity hint: Up to 240 mm² can be connected depending on the cable manufacturer.
300 V AC (between the auxiliary contacts)
2000 operations at 690 V AC-3
5000 operations at 400 V AC-1
3000 operations at 690 V AC-1
2000 operations at 400 V AC-3
5000 operations at 415 V AC-1
Built-in device plug-in technique
IP20
IP66 (with door coupling rotary handle)
IP00 (terminations, phase isolator and strip terminal)
Damp heat, constant, to IEC 60068-2-78
The circuit-breaker fulfills all requirements for AC-3 switching category.
R.m.s. value measurement and “thermal memory”
Adjustable time delay setting to overcome current peaks tr at 6 x Ir also infinity (without overload releases)
All AC-3 rating data applies to direct switching by the circuit-breaker under normal operating conditions. If, for example, a contactor takes over AC-3 switching under normal operating conditions, the full rated uninterrupted current applies to the circuit-breaker, In = Iu.
Maximum back-up fuse, if the expected short-circuit currents at the installation location exceed the switching capacity of the circuit breaker (Rated short-circuit breaking capacity Icn)
Rated current = rated uninterrupted current: 250 A
Terminal capacity hint: Up to 240 mm² can be connected depending on the cable manufacturer.
0.75 mm² - 2.5 mm² (1x)
25 mm² - 185 mm² (1x) at tunnel terminal
50 mm² - 240 mm² (1x) at 2-hole tunnel terminal
M10 at rear-side screw connection
Max. 10 mm x 50 mm (2x) at rear-side width extension
Min. 20 mm x 5 mm direct at switch rear-side connection
16 mm² (1x) direct at switch rear-side connection
16 mm² (1x) at tunnel terminal
16 mm² (2x) direct at switch rear-side connection
300 mm² (2x) at rear-side width extension
16 mm² - 185 mm² (1x) at 1-hole tunnel terminal
25 mm² - 240 mm² (1x) direct at switch rear-side connection
25 mm² - 240 mm² (2x) direct at switch rear-side connection
25 mm² - 120 mm² (2x) at box terminal
Min. 6 segments of 16 mm x 0.8 mm at rear-side connection (punched)
Min. 6 segments of 16 mm x 0.8 mm at box terminal
10 segments of 50 mm x 1 mm (2x) at rear-side width extension
Max. 10 segments of 24 mm x 1 mm + 5 segments of 24 mm x 1 mm at box terminal
Max. 10 segments of 32 mm x 1 mm + 5 segments of 32 mm x 1 mm at rear-side connection (punched)
Motor protection with class 1 energy metering