View larger
NZMH2-S160-CNA 269273 Y7-269273 EATON ELECTRIC NZMH2-S160-CNA
NZMH2-S160-CNA
269273
Y7-269273
EATON - MOELLER
1 Pcs.
Automation > Motor protection circuit-breaker
Circuit Breakers NZM
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Eaton Moeller NZMH2-S160-CNA circuit breaker provides robust magnetic short-circuit protection for heavy-duty industrial power distribution systems and feeder lines. These reliable components safeguard downstream equipment by swiftly interrupting high fault currents in demanding electrical installations.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Overload release current setting (EF002336): 0 A
- Adjustment range undelayed short-circuit release (EF007131): 1280 A
- With thermal overload protection (EF006233): No
- Phase failure sensitive (EF007400): No
- Switch off technique (EF007007): Magnetic
- Rated operating voltage (EF001435): 690 V
- Rated permanent current Iu (EF001389): 160 A
- Rated operation power at AC-3, 230 V (EF007025): 45 kW
- Rated operation power at AC-3, 400 V (EF001364): 90 kW
- Type of electrical connection of main circuit (EF006819): Screw connection
- Type of control element (EF006976): Rocker lever
- Device construction (EF008240): Built-in device fixed built-in technique
- With integrated auxiliary switch (EF001387): No
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
- Degree of protection (IP) (EF005474): IP20
More info
▲General specifications
UL/CSA
UL (Category Control Number DKPU2)
CSA certified
Specially designed for North America
IEC/EN 60947
CSA (File No. 22086)
UL (File No. E31593)
CE marking
UL listed
CSA-C22.2 No. 5-09
IEC
CSA (Class No. 1432-01)
IEC 60947-2
Product specifications
- Branch circuits, feeder circuits
- Use in unearthed supply systems at 690 V
Fixed
Damp heat, cyclic, to IEC 60068-2-30
500 V AC (between auxiliary contacts and main contacts)
IP20
300 A (415 V AC-1, making and breaking capacity)
160 A (690 V AC-1, making and breaking capacity)
160 A (660-690 V AC-3, making and breaking capacity)
IP40 (with insulating surround)
IP00 (terminations, phase isolator and strip terminal)
Min. 2 segments of 9 mm x 0.8 mm at box terminal
Min. 2 segements of 16 mm x 0.8 mm at rear-side connection (punched)
Max. 10 segments of 16 mm x 0.8 mm at box terminal
6500 operations at 415 V AC-3
10000 operations at 400 V AC-1
5000 operations at 690 V AC-3
7500 operations at 690 V AC-1
14 mm² - 18 mm² (1x)
Max. 20 mm x 5 mm direct at switch rear-side connection
Min. 16 mm x 5 mm direct at switch rear-side connection
6 mm² - 11 mm² (1x) direct at switch rear-side connection
6 mm² (1x) at tunnel terminal
4 mm² - 350 mm² (1x) at tunnel terminal
4 mm² - 3/0 mm² (1x) direct at switch rear-side connection