Automatic int. NZM2 PXR25, 90A, 3p, screw terminal, UL/CSA The xEffect NZM...-PMX-NA circuit breaker range with power expert release (PXR) electronic triggering system covers use cases for motor protection with only four compact sizes and is suitable for the IEC market. The integrated energy measuring function supplies currents, voltages and active energy (kWh) with accuracy class 1 according to IEC 61557-12. Test function and settings via micro USB port directly on the switch. Modular function groups always make mounting flexible and may be supplemented by the comprehensive range of accessories. R.m.s. value measurement and thermal memory.

Automation > Motor protection circuit-breaker
Circuit Breakers NZM

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

NZMH2-PMX90-NA by Eaton Moeller is an automatic industrial circuit breaker designed for high-capacity electrical distribution networks and motor branch circuits. These robust switching components protect electrical infrastructure against overcurrent and short-circuit faults while supporting safe maintenance operations in demanding industrial facilities. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Overload release current setting (EF002336): 36 A
  • Adjustment range undelayed short-circuit release (EF007131): 180 A
  • With thermal overload protection (EF006233): Yes
  • Phase failure sensitive (EF007400): Yes
  • Switch off technique (EF007007): Electronic
  • Rated operating voltage (EF001435): 690 V
  • Rated permanent current Iu (EF001389): 90 A
  • Rated operation power at AC-3, 230 V (EF007025): 22 kW
  • Rated operation power at AC-3, 400 V (EF001364): 45 kW
  • Type of electrical connection of main circuit (EF006819): Screw connection
  • Type of control element (EF006976): Rocker lever
  • Device construction (EF008240): Built-in device fixed built-in technique
  • With integrated auxiliary switch (EF001387): No
  • With integrated under voltage release (EF001390): No
  • Number of poles (EF001391): 3
  • Degree of protection (IP) (EF005474): IP20

Product Datasheet