View larger
NZMB2-M125-BT 115260 EATON ELECTRIC Circuit-breaker, 3p, 125A, box terminals
NZMB2-M125-BT
115260
EATON - MOELLER
1 Pcs.
Automation > Motor protection circuit-breaker
Circuit Breakers NZM
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Eaton Moeller NZMB2-M125-BT circuit-breaker acts as an industrial protective device designed specifically for motor circuit applications, featuring integrated box terminals for secure conductor attachment. These units protect distribution systems and connected machinery against excessive thermal and magnetic current loads. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Overload release current setting (EF002336): 100 A
- Adjustment range undelayed short-circuit release (EF007131): 1000 A
- With thermal overload protection (EF006233): Yes
- Phase failure sensitive (EF007400): No
- Switch off technique (EF007007): Thermomagnetic
- Rated operating voltage (EF001435): 440 V
- Rated permanent current Iu (EF001389): 125 A
- Rated operation power at AC-3, 230 V (EF007025): 37 kW
- Rated operation power at AC-3, 400 V (EF001364): 55 kW
- Type of control element (EF006976): Rocker lever
- Device construction (EF008240): Built-in device fixed built-in technique
- With integrated auxiliary switch (EF001387): No
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
- Degree of protection (IP) (EF005474): IP20
- Height (EF000040): 206 mm
More info
▲Delivery program
IEC/EN 60947-4-1, IEC/EN 60947-2
The circuit-breaker fulfills all requirements for AC-3 switching category.