EATON - MOELLER NZM4-XA24AC/DC-PI NZM4-XA24AC/DC-PI 189805 Y7-189805 EATON ELECTRIC NZM4-XA24AC/DC-PI View larger
Images are for illustrative purposes only. Please refer to data sheet for details

NZM4-XA24AC/DC-PI 189805 Y7-189805 EATON ELECTRIC NZM4-XA24AC/DC-PI

NZM4-XA24AC/DC-PI

189805

Y7-189805

EATON - MOELLER

1 Pcs.

NZM4-XA24AC/DC-PI NZM4-XA24AC/DC-PI. Shunt release for NZM4, 24AC/DC, Push-in terminals Optional accessories for the circuit-breaker series NZM offers a comprehensive portfolio of application options for use world wide. The mounting is always flexible and easy thanks to the modular function groups. Notes: Shunt releases with push-in terminals. Switches are tripped by a voltage pulse or by the application of uninterrupted voltage. When the shunt release is live, contact with the circuit-breaker's main contacts on switching on is reliably prevented. Shunt release modules cannot be installed simultaneously with early-make contact NZM…-XHIV, untervoltage release NZM…-XU…, or relais modules NZM...-X2A...

Automation > Shunt release (for power circuit breaker)
Circuit Breakers NZM

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

General specifications

Product Name
Eaton Moeller series NZM release
Catalog Number
189805
Model Code
NZM4-XA24AC/DC-PI
EAN
4015081878000
Product Length/Depth
110 mm
Product Height
63 mm
Product Width
62 mm
Product Weight
0.245 kg
Compliances
IEC
UL/CSA

Product specifications

Type
AccessoryShunt release
Special features
When the shunt release is live, contact with the circuit-breaker's main contacts on switching on is reliably prevented.Shunt release modules cannot be installed simultaneously with early-make contact NZM…-XHIV, untervoltage release NZM…-XU…, or relais modules NZM...-X2A...
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Electric connection type
Screw connection
Frame
NZM4
Used with
NZM4(-4), N(S)4(-4)
Number of contacts (normally open contacts)
0
Rated control supply voltage
24 V AC/DC
Rated control supply voltage (Us) at AC, 50 Hz - max
24 V
Rated control supply voltage (Us) at AC, 50 Hz - min
24 V
Rated control supply voltage (Us) at AC, 60 Hz - max
24 V
Rated control supply voltage (Us) at AC, 60 Hz - min
24 V
Suitable for
Motor safety switch
Off-load switch
Connection type
With push in terminal
Voltage type
AC
Rated control supply voltage (Us) at DC - max
24 V
Rated control supply voltage (Us) at DC - min
24 V
Number of contacts (normally closed contacts)
0
Number of contacts (change-over contacts)
0
Undelayed short-circuit release - min
0 A
Undelayed short-circuit release - max
0 A

ETIM for 189805 Low-voltage industrial controls and switchgear (EC001023)
Feature Name Feature Value
Rated control supply voltage AC 50 Hz (EF003978) 24 V
Rated control supply voltage AC 60 Hz (EF003979) 24 V
Rated control supply voltage DC (EF003980) 24 V
Voltage type for actuating (EF008242) AC
Initial value of the undelayed short-circuit release - setting range (EF008187) 0 A
End value adjustment range undelayed short-circuit release (EF008188) 0 A
Type of electric connection (EF003961) Screw connection
Number of contacts as normally open contact (EF008256) 0
Number of contacts as normally closed contact (EF008255) 0
Number of contacts as change-over contact (EF008257) 0
Suitable for power circuit breaker (EF005863) No
Suitable for off-load switch (EF001543) Yes
Suitable for motor safety switch (EF005826) Yes
Suitable for overload relay (EF001545) No

Product Datasheet