Type
AccessoryUndervoltage releaseUndervoltage release with early-make auxiliary contact and two relays
Special features
For interlock circuits, load-shedding circuits, make-before-break interruption of shunt trip for primary breaker useInstantaneous shut-off NZM breaker at control voltage below 35-70% UsFor emergency-stop devices with an emergency-stop buttonFor breaker's signalizing commands/different states2 relays/unitTrip unit config of activation criteriaConfig by communication/breaker display/front USB port/Eaton Power Xpert Protection ManagerSwitched off under-voltage trip: accidental contact with breaker’s primary contacts is prevented when switched onAuxiliary contact make-before-break activation when manual switching on and off: ~20 ms(NZM2/3)/90 ms(NZM4)For use with electronic trip breakers except NZM...-XR...Under-voltage trip relay modules incompatbile with NZM...-XHIV, NZM...-XU..., NZM...-XA.Trip unit controlled relay coilPush-in clamp relay contacts for control wiring.Relays use for controlling remote operator at Us=208-204 V ACIncompatible with PXR10 NZM-AX
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Fitted with:
Early-make auxiliary contact and 2 relays
Used with
PXR20(25) NZM3(-4)-..X…
PXR20(25) NZM2(-4)-..X…
Minimum command time - max
Minimum command time - min
Number of contacts (normally open contacts)
Pick-up power consumption at AC (undervoltage release)
Pick-up power consumption at DC (undervoltage release)
Rated control supply voltage (Us) at AC, 50 Hz - max
Rated control supply voltage (Us) at AC, 50 Hz - min
Rated control supply voltage (Us) at AC, 60 Hz - max
Rated control supply voltage (Us) at AC, 60 Hz - min
Rated insulation voltage (Ui)
Strip length
8 mm (relay contact connection)
Switching capacity (reference value) - min
Rated impulse withstand voltage (Uimp)
Suitable for
Motor safety switch
Off-load switch
Drop-out voltage of undervoltage release AC/DC - max
Rated operational current
1 A (230 V AC-1, relay contacts)
1 A (24 V AC-1, relay contacts)
1 A (110 V AC-1, relay contacts)
1 A (24 V DC-1, relay contacts)
Drop-out voltage of undervoltage release AC/DC - min
Power consumption
0.8 W (sealing DC)
1.5 VA (sealing AC)
Rated control supply voltage (Us) at DC - max
Rated control supply voltage (Us) at DC - min
Number of contacts (normally closed contacts)
Number of contacts (change-over contacts)
Undelayed short-circuit release - min
Undelayed short-circuit release - max
Terminal capacity (stranded cable)
0.25 mm² - 0.75 mm² (1x) for undervoltage release with uninsulated end sleeve in accordance with DIN46228 / 1
0.25 mm² - 0.75 mm² (1x) for undervoltage release
0.25 mm² - 1.5 mm² (1x) for undervoltage release with insulated end sleeve in accordance with DIN46224 / 4
0.25 mm² - 1.5 mm² (1x) at shunt release
24 - 16 AWG (1x) at shunt release
0.25 mm² - 1.5 mm² (1x) for undervoltage release
24 - 16 AWG (1x) for undervoltage release
Terminal capacity (solid cable)
0.2 mm² - 1.5 mm² (1x) at shunt release
0.2 mm² - 1.5 mm² (1x) for undervoltage release
Rated control voltage (relay contacts)