NZM2/3-XA2A208-240AC 189743 Y7-189743 EATON ELECTRIC NZM2/3-XA2A208-240AC
NZM2/3-XA2A208-240AC
189743
Y7-189743
EATON - MOELLER
1 Pcs.
Automation > Shunt release (for power circuit breaker)
Circuit Breakers NZM
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Shunt release NZM2/3-XA2A208-240AC 189743 Y7-189743 EATON ELECTRIC NZM2/3-XA2A208-240AC acts as an accessory for circuit breakers and switches, allowing for remote tripping and electrical opening of the main protective device upon command.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 208 V
- Rated control supply voltage AC 60 Hz (EF003979): 208 V
- Rated control supply voltage DC (EF003980): 0 V
- Voltage type for actuating (EF008242): AC
- Type of electric connection (EF003961): Screw connection
- Number of contacts as normally open contact (EF008256): 2
- Number of contacts as normally closed contact (EF008255): 0
- Number of contacts as change-over contact (EF008257): 0
- Suitable for power circuit breaker (EF005863): No
- Suitable for off-load switch (EF001543): Yes
- Suitable for motor safety switch (EF005826): Yes
- Suitable for overload relay (EF001545): No
More info
▲General specifications
IEC
RoHS conform
CE marking
CSA-C22.2 No. 5-09
CSA (Class No. 1437-01)
CSA (File No. 22086)
UL (Category Control Number DIHS)
UL (File No. E140305)
IEC60947
UL489
UL listed
Product specifications
- The breakers are actuated by a voltage pulse or by applying a no-break current.
- For signalizing commands or different states of the circuit-breaker.
- Two relays per unit.
- The activation criteria can be configured in the trip unit.
- Configuration via communication or circuit breaker display or front USB port and Eaton Power Xpert Protection Manager.
- If the shunt trip is live, contact with the circuit breaker’s primary contacts is prevented when switched on.
- Only for use in combination with circuit-breakers with electronic trips.
- Shunt trip relay modules cannot be installed simultaneously with make-before-break auxiliary contact NZM...-XHIV, under-voltage trip NZM...-XU... or shunt trip NZM...-XA.
- Relay coil is controlled by trip unit.
- Relay contacts for control wiring.
- Relays can be used for controlling remote operator with Us=208-204 V AC.
- Control wiring on push-in clamps.
- Cannot be used with the PXR10 NZM-AX electronic trip.
PXR20(25) NZM2(-4)-..X…
Off-load switch
1 A (110 V AC-1, relay contacts)
1 A (230 V AC-1, relay contacts)
0.25 mm² - 1.5 mm² (1x) at shunt release (insulated ferrule according to DIN46224 / 4)
0.25 mm² - 1.5 mm² (1x) at shunt release
24 - 16 AWG (1x) for undervoltage release
0.25 mm² - 0.75 mm² (1x) at shunt release (uninsulated ferrule according to DIN46228 / 1)
24 - 16 AWG (1x) at shunt release
0.2 mm² - 1.5 mm² (1x) for undervoltage release
24 V AC
208 V AC
240 V AC