View larger
DILET70-W
048899
EATON - MOELLER
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Product range | DILET timing relays | ||
Basic function | Timer relays | ||
Function | Multi-functional On-delayed Off-delayed Fleeting contact on energization Fleeting contact on de-energization Flashing, pulse initiating On- and Off-delayed Pulse forming Pulse generating | ||
| with connection for potentiometer Adjustable timing functions | |||
Number of changeover contacts | 1 | ||
Time range | 0.05 s - 60 h | ||
Time range | 0.05 - 1s 0.15 - 3 s 0.5 - 10 s 3 - 60 s 0,15 - 3 min 0.5 - 10 min 3 - 60 min 0.15 - 3 h 0.5 - 10 h 3 - 60 h | ||
Rated operational current | |||
AC-11 | |||
230 V | Ie | A | 3 |
380 V 400 V 415 V | Ie | A | 3 |
AC-15 | |||
220 V 230 V 240 V | Ie | A | 3 |
Voltage range | ULN | V | 400 V AC, 50/60 Hz |
Width | mm | 45 | |
| Terminal marking according to EN 50042 | |||
| General | |||
Standards | Standard IEC/EN 61812 VDE 0435 | ||
Lifespan, mechanical | |||
AC operated | Operations | x 106 | 30 |
DC operated | Operations | x 106 | 30 |
Climatic proofing | Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30 | ||
Ambient temperature | |||
Open | °C | -20 - +60 | |
Enclosed | °C | - 20 - + 45 | |
Mounting position | As required | ||
Mechanical shock resistance (IEC/EN 60068-2-27) | |||
Half-sinusoidal shock, 20 ms | g | ||
Make contact | g | 4 | |
Degree of protection | |||
Terminals | IP20 | ||
Weight | kg | 0.09 | |
Terminal capacities | mm2 | ||
Solid | mm2 | 1 x (0.75 - 2.5) 2 x (0.75 - 2.5) | |
Flexible with ferrule | mm2 | 1 x (0.75 - 1.5) 2 x (0.75 - 1.5) | |
Solid or stranded | AWG | 1 x (18 - 14) | |
| Contacts | |||
Rated impulse withstand voltage | Uimp | V AC | 6000 |
Overvoltage category/pollution degree | III/2 | ||
Rated insulation voltage | Ui | V AC | 600 |
Rated operational voltage | Ue | V AC | 440 |
Safe isolation to EN 61140 | |||
between coil and auxiliary contacts | V AC | 250 | |
between the auxiliary contacts | V AC | 250 | |
Making capacity | |||
AC-14 cos ϕ = 0.3400 V | A | 48 | |
AC-15 cos ϕ = 0.3 220 V | A | 50 | |
DC-11 L/R - 40 ms | x Ie | 1.1 | |
Breaking capacity | |||
AC-14 cos ϕ = 0.3440 V | A | 3 | |
AC-15 cos ϕ = 0.3220 V | A | 3 | |
DC-11 L/R - 40 ms | x Ie | 1.1 | |
Rated operational current | Ie | A | |
AC--14 | |||
440 V | Ie | A | 3 |
AC-15 | |||
220 V 230 V 240 V | Ie | A | 3 |
DC-11 | |||
Note | Making and breaking conditions to DC13, time constant as stated | ||
L/R max. 15 ms | A | ||
24 V | Ie | A | 1.5 |
L/R max. 50 ms | A | 1.2 | |
Conv. thermal current | Ith | A | 6 |
Short-circuit rating without welding | |||
Note | When supplied directly from mains or transformer > 1000 VA | ||
Max. fuse, make contacts | A gG/gL | 6 | |
Max. fuse, break contacts | A gG/gL | 6 | |
| Magnet systems | |||
Rated operational voltage | Ue | V | |
AC | 400 | ||
Voltage tolerance | x Uc | ||
Pick-up voltage | x Us | ||
Min. pick-up voltage, AC operated | x Uc | 0.85 | |
Pick-up voltage AC operated, max. | x Uc | 1.1 | |
Power consumption | |||
Pick-up AC | VA | 0.5 | |
Sealing AC | VA | 0.5 | |
Duty factor | % DF | 100 | |
Maximum operating frequency | Ops/h | 4000 | |
Minimum command time | |||
AC | ms | 50 | |
Repetition accuracy (deviation) | % | ||
Technical data for design verification | |||
Rated operational current for specified heat dissipation | In | A | 6 |
Heat dissipation per pole, current-dependent | Pvid | W | 0.9 |
Equipment heat dissipation, current-dependent | Pvid | W | 0 |
Static heat dissipation, non-current-dependent | Pvs | W | 0.5 |
Heat dissipation capacity | Pdiss | W | 0 |
Operating ambient temperature min. | °C | -20 | |
Operating ambient temperature max. | °C | 60 | |
IEC/EN 61439 design verification | |||
10.2 Strength of materials and parts | |||
10.2.2 Corrosion resistance | Meets the product standard's requirements. | ||
10.2.3.1 Verification of thermal stability of enclosures | Meets the product standard's requirements. | ||
10.2.3.2 Verification of resistance of insulating materials to normal heat | Meets the product standard's requirements. | ||
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects | Meets the product standard's requirements. | ||
10.2.4 Resistance to ultra-violet (UV) radiation | Meets the product standard's requirements. | ||
10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. | ||
10.2.6 Mechanical impact | Does not apply, since the entire switchgear needs to be evaluated. | ||
10.2.7 Inscriptions | Meets the product standard's requirements. | ||
10.3 Degree of protection of ASSEMBLIES | Does not apply, since the entire switchgear needs to be evaluated. | ||
10.4 Clearances and creepage distances | Meets the product standard's requirements. | ||
10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. | ||
10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. | ||
10.7 Internal electrical circuits and connections | Is the panel builder's responsibility. | ||
10.8 Connections for external conductors | Is the panel builder's responsibility. | ||
10.9 Insulation properties | |||
10.9.2 Power-frequency electric strength | Is the panel builder's responsibility. | ||
10.9.3 Impulse withstand voltage | Is the panel builder's responsibility. | ||
10.9.4 Testing of enclosures made of insulating material | Is the panel builder's responsibility. | ||
10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. | ||
10.11 Short-circuit rating | Is the panel builder's responsibility. The specifications for the switchgear must be observed. | ||
10.12 Electromagnetic compatibility | Is the panel builder's responsibility. The specifications for the switchgear must be observed. | ||
10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. | ||
| Relays (EG000019) / Timer relay (EC001439) | |||
| Electric engineering, automation, process control engineering / Low-voltage switch technology / Relay and socket / Timed relay ([email protected] [AKF092010]) | |||
Type of electric connection | Screw connection | ||
Function delay-on energization | Yes | ||
Function delay on de-energization | Yes | ||
Function floating contact on energization | Yes | ||
Function floating contact on de-energization | Yes | ||
Function star-delta | No | ||
Function pulse shaping | Yes | ||
Function flashing, starting with pause, fixed time | Yes | ||
Function flashing, starting with pulse, fixed time | Yes | ||
Clock function, starting with pause, variable | Yes | ||
Clock function, starting with pulse, variable | Yes | ||
With plug-in socket | No | ||
Remote operation possible | Yes | ||
Suitable only for remote control | No | ||
Pluggable on auxiliary contact block | No | ||
Rated control supply voltage Us at AC 50HZ | V | 400 - 400 | |
Rated control supply voltage Us at AC 60HZ | V | 400 - 400 | |
Rated control supply voltage Us at DC | V | 0 - 0 | |
Voltage type for actuating | AC | ||
Time range | s | 0.05 - 216000 | |
Number of outputs, undelayed, normally closed contact | 0 | ||
Number of outputs, undelayed, normally open contact | 0 | ||
Number of outputs, undelayed, change-over contact | 1 | ||
Number of outputs, delayed, normally closed contact | 0 | ||
Number of outputs, delayed, normally open contact | 0 | ||
Number of outputs, delayed, change-over contact | 1 | ||
Outputs, reversible delayed/undelayed | Yes | ||
With semiconductor output | No | ||
Width | mm | 45 | |
Height | mm | 58 | |
Depth | mm | 52 | |
| Feature Name | Feature Value |
|---|---|
| Type of electric connection (EF003961) | Screw connection |
| Complete with socket (EF003359) | No |
| Suitable for DIN rail (top hat rail) mounting (EF007250) | No |
| Suitable for front mounting (EF020288) | No |
| Pluggable on auxiliary contact block (EF006952) | No |
| Function delay-on energization (EF003374) | Yes |
| Function delay on de-energization (EF003401) | Yes |
| Function floating contact on energization (EF003378) | Yes |
| Function floating contact on de-energization (EF003402) | Yes |
| Function star-delta (EF003380) | No |
| Function pulse shaping (EF003403) | Yes |
| Function flashing, starting with pause, fixed time (EF003363) | Yes |
| Function flashing, starting with pulse, fixed time (EF003364) | Yes |
| Clock function, starting with pause, variable (EF003365) | Yes |
| Clock function, starting with pulse, variable (EF003366) | Yes |
| Time range (EF003384) | 0.05 s |
| Remote operation possible (EF003361) | Yes |
| Suitable as remote control (EF003362) | No |
| Rated control supply voltage AC 50 Hz (EF003978) | 400 V |
| Rated control supply voltage AC 60 Hz (EF003979) | 400 V |
| Rated control supply voltage DC (EF003980) | 0 V |
| Voltage type for actuating (EF008242) | AC |
| Number of outputs, undelayed, normally closed contact (EF006835) | 0 |
| Number of outputs, undelayed, normally open contact (EF006836) | 0 |
| Number of outputs, undelayed, change-over contact (EF006837) | 1 |
| Number of outputs, delayed, normally closed contact (EF006838) | 0 |
| Number of outputs, delayed, normally open contact (EF006839) | 0 |
| Number of outputs, delayed, change-over contact (EF006840) | 1 |
| Outputs, reversible delayed/undelayed (EF006988) | Yes |
| With semiconductor output (EF003373) | No |
| Width (EF000008) | 45 mm |
| Height (EF000040) | 58 mm |
| Depth (EF000049) | 52 mm |