EATON - MOELLER MSC-D-1,6-M7(230V50HZ)-PI MSC-D-1,6-M7(230V50HZ)-PI 199565 Y7-199565 EATON ELECTRIC MSC-D-1,6-M7(230V50HZ)-PI View larger
Images are for illustrative purposes only. Please refer to data sheet for details

MSC-D-1,6-M7(230V50HZ)-PI 199565 Y7-199565 EATON ELECTRIC MSC-D-1,6-M7(230V50HZ)-PI

MSC-D-1,6-M7(230V50HZ)-PI

199565

Y7-199565

EATON - MOELLER

1 Pcs.

MSC-D-1,6-M7(230V50HZ)-PI Eaton Moeller® series MSC-D DOL starter, 380 V 400 V 415 V: 0.37, 0.55 kW, Ir= 1 - 1.6 A, 230 V 50 Hz, 240 V 60 Hz, AC, Push in terminals DOL starter, Basic device: MSC, Notes: Also suitable for motors with efficiency class IE3., IE3-ready devices are identified by the logo on their packaging., Motor ratings Motor rating AC-3 380 V 400 V 415 V: P= 0.37, 0.55 kW, Setting range of overload releases: Ir= 1 - 1.6 A, Coordination: Type of coordination “1”, Type of coordination “2”, Actuating voltage: 230 V 50 Hz, 240 V 60 Hz, AC voltage, Standards: IEC/EN 60947-4-1, VDE 0660

Automation > Motor starter/Motor starter combination
Circuit Breakers PKZ

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Direct starter MSC-D-1,6-M7(230V50HZ)-PI from Eaton Moeller offers reliable motor control and overload protection for standard industrial drives. Factory-combined switching components reduce engineering and wiring effort while ensuring safe operational performance in control panels.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Type of motor starter (EF009598): Direct starter
  • With short-circuit release (EF006691): Yes
  • Rated control supply voltage AC 50 Hz (EF003978): 230 V
  • Rated control supply voltage AC 60 Hz (EF003979): 0 V
  • Rated control supply voltage DC (EF003980): 0 V
  • Voltage type for actuating (EF008242): AC
  • Rated operation power at AC-3, 230 V, 3-phase (EF009599): 0.25 kW
  • Rated operation power at AC-3, 400 V (EF001364): 0.55 kW
  • Rated power, 460 V, 60 Hz, 3-phase (EF009600): 0 kW
  • Rated power, 575 V, 60 Hz, 3-phase (EF009601): 0 kW
  • Rated operation current Ie (EF001443): 1.5 A
  • Rated operation current at AC-3, 400 V (EF009602): 1.6 A
  • Overload release current setting (EF002336): 1 A
  • Power consumption (EF000346): 1.4 W
  • Ambient temperature, upper operating limit (EF009603): 55 °C
  • Temperature compensated overload protection (EF009604): Yes

More info

▲

General specifications

Product Name
Eaton Moeller® series MSC-D DOL starter
Catalog Number
199565
Model Code
MSC-D-1,6-M7(230V50HZ)-PI
EAN
4015081982660
Product Length/Depth
95 mm
Product Height
197 mm
Product Width
45 mm
Product Weight
0.601 kg
Certifications
VDE 0660
IEC/EN 60947-4-1
Catalog Notes
Also suitable for motors with efficiency class IE3.

Product specifications

Type
Starter with Bi-Metal release
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Fitted with:
Short-circuit release
Pollution degree
3
Class
CLASS 10 A
Connection to SmartWire-DT
No
Rated impulse withstand voltage (Uimp)
6000 V AC
Model
IEC/UL starter
Altitude
Max. 2000 m
Electrical connection type of main circuit
Spring clamp connection
Voltage type
AC
Mounting method
DIN rail
Overvoltage category
III
Connection
Push in terminals
Functions
Temperature compensated overload protection
Overload release current setting - min
1 A
Rated conditional short-circuit current (Iq), type 2, 230 V
50 A
Rated conditional short-circuit current (Iq), type 2, 380 V, 400 V, 415 V
50 A
Rated conditional short-circuit current, type 1, 480 Y/277 V
0 A
Rated conditional short-circuit current, type 1, 600 Y/347 V
0 A
Rated control supply voltage (Us) at AC, 50 Hz - max
230 V
Rated control supply voltage (Us) at AC, 50 Hz - min
230 V
Rated control supply voltage (Us) at AC, 60 Hz - max
0 V
Rated control supply voltage (Us) at AC, 60 Hz - min
0 V
Rated control supply voltage (Us) at DC - max
0 V
Rated control supply voltage (Us) at DC - min
0 V
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V
1.6 A
Power consumption, sealing, 50 Hz
1.4 W, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz
Rated operational current (Ie)
1.5 A
Rated operational voltage
230 - 415 V AC
Suitable for
Also motors with efficiency class IE3
Ambient operating temperature - max
55 °C
Ambient operating temperature - min
-25 °C
Coordination type
2
Number of auxiliary contacts (normally closed contacts)
0
Number of auxiliary contacts (normally open contacts)
1
Number of command positions
0
Number of pilot lights
0
Overload release current setting - max
1.6 A
Rated operational power at AC-3, 220/230 V, 50 Hz
0.25 kW
Rated operational power at AC-3, 380/400 V, 50 Hz
0.55 kW
Rated power at 460 V, 60 Hz, 3-phase
0 kW
Rated power at 575 V, 60 Hz, 3-phase
0 kW
Short-circuit release (Irm) - max
24.8 A
Coordination class (IEC 60947-4-3)
Class 2
Degree of protection
IP20
NEMA Other
Electrical connection type for auxiliary- and control-current circuit
Spring clamp connection
Actuating voltage
230 V 50 Hz
240 V 60 Hz
Power consumption
1.4 W

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.