MSC-D-0,63-M7(230V50HZ)-PI Eaton Moeller® series MSC-D DOL starter, 380 V 400 V 415 V: 0.12, 0.18 kW, Ir= 0.4 - 0.63 A, 230 V 50 Hz, 240 V 60 Hz, AC, Push in terminals DOL starter, Basic device: MSC, Notes: Also suitable for motors with efficiency class IE3., IE3-ready devices are identified by the logo on their packaging., Motor ratings Motor rating AC-3 380 V 400 V 415 V: P= 0.12, 0.18 kW, Setting range of overload releases: Ir= 0.4 - 0.63 A, Coordination: Type of coordination “1”, Type of coordination “2”, Actuating voltage: 230 V 50 Hz, 240 V 60 Hz, AC voltage, Standards: IEC/EN 60947-4-1, VDE 0660

Automation > Motor starter/Motor starter combination
Circuit Breakers PKZ

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

MSC-D-0,63-M7(230V50HZ)-PI Eaton Moeller MSC-D-0,63-M7(230V50HZ)-PI 199563 Y7-199563 Eaton Electric MSC-D-0,63-M7(230V50HZ)-PI is a direct starter utilized for starting and protecting standard industrial electric motors. Compact modular starters provide coordinated short-circuit and overload protection in electrical distribution panels.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Type of motor starter (EF009598): Direct starter
  • With short-circuit release (EF006691): Yes
  • Rated control supply voltage AC 50 Hz (EF003978): 230 V
  • Rated control supply voltage AC 60 Hz (EF003979): 0 V
  • Rated control supply voltage DC (EF003980): 0 V
  • Voltage type for actuating (EF008242): AC
  • Rated operation power at AC-3, 230 V, 3-phase (EF009599): 0.09 kW
  • Rated operation power at AC-3, 400 V (EF001364): 0.12 kW
  • Rated power, 460 V, 60 Hz, 3-phase (EF009600): 0 kW
  • Rated power, 575 V, 60 Hz, 3-phase (EF009601): 0 kW
  • Rated operation current Ie (EF001443): 0.6 A
  • Rated operation current at AC-3, 400 V (EF009602): 0.63 A
  • Overload release current setting (EF002336): 0.63 A
  • Power consumption (EF000346): 1.4 W
  • Ambient temperature, upper operating limit (EF009603): 55 °C
  • Temperature compensated overload protection (EF009604): Yes

More info

General specifications

Product Name
Eaton Moeller® series MSC-D DOL starter
Catalog Number
199563
Model Code
MSC-D-0,63-M7(230V50HZ)-PI
EAN
4015081982646
Product Length/Depth
95 mm
Product Height
197 mm
Product Width
45 mm
Product Weight
0.569 kg
Certifications
IEC/EN 60947-4-1
VDE 0660
Catalog Notes
Also suitable for motors with efficiency class IE3.

Features & Functions

Fitted with:
Short-circuit release
Functions
Temperature compensated overload protection

General

Class
CLASS 10 A
Connection
Push in terminals
Connection to SmartWire-DT
No
Coordination type
2
Degree of protection
IP20
NEMA Other
Model
IEC/UL starter
Mounting method
DIN rail
Number of auxiliary contacts (normally closed contacts)
0
Number of auxiliary contacts (normally open contacts)
1
Overload release current setting - min
0.63 A
Overload release current setting - max
0.63 A
Overvoltage category
III
Pollution degree
3
Rated impulse withstand voltage (Uimp)
6000 V AC
Suitable for
Also motors with efficiency class IE3
Type
Starter with Bi-Metal release
Voltage type
AC

Climatic environmental conditions

Altitude
Max. 2000 m
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
55 °C

Electrical rating

Rated operational current (Ie)
0.6 A
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V
0.63 A
Rated operational power at AC-3, 220/230 V, 50 Hz
0.09 kW
Rated operational power at AC-3, 380/400 V, 50 Hz
0.12 kW
Rated operational voltage
230 - 415 V AC

Short-circuit rating

Rated conditional short-circuit current (Iq), type 2, 380 V, 400 V, 415 V
50 A
Short-circuit release (Irm) - max
9.8 A

Magnet system

Power consumption, sealing, 50 Hz
1.4 W, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz
Rated control supply voltage (Us) at AC, 50 Hz - min
230 V
Rated control supply voltage (Us) at AC, 50 Hz - max
230 V
Rated control supply voltage (Us) at AC, 60 Hz - min
0 V
Rated control supply voltage (Us) at AC, 60 Hz - max
0 V
Rated control supply voltage (Us) at DC - min
0 V
Rated control supply voltage (Us) at DC - max
0 V

Design verification

10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.