View larger
PKZM0-0,25-SC 229829 XTPRSCP25BC1NL EATON ELECTRIC Motor-protective circuit-breaker, 3p, Ir 0.16-0.25A, scre..
PKZM0-0,25-SC
229829
XTPRSCP25BC1NL
EATON - MOELLER
1 Pcs.
Automation > Motor protection circuit-breaker
Circuit Breakers PKZ
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Motor-protective circuit-breaker, 3p, Ir 0.16-0.25A, scre devices are integrated into industrial control cabinets to provide dedicated overload and short-circuit protection for low-amperage electric motors. By interrupting dangerous currents promptly, they help prevent motor damage and unscheduled facility downtime. The Eaton Moeller PKZM0-0,25-SC unit delivers dependable switching control. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Overload release current setting (EF002336): 0.16 A
- Adjustment range undelayed short-circuit release (EF007131): 3.9 A
- With thermal overload protection (EF006233): No
- Phase failure sensitive (EF007400): Yes
- Switch off technique (EF007007): Thermomagnetic
- Rated operating voltage (EF001435): 690 V
- Rated permanent current Iu (EF001389): 0.25 A
- Rated operation power at AC-3, 230 V (EF007025): 0 kW
- Rated operation power at AC-3, 400 V (EF001364): 0.06 kW
- Power loss (EF005387): 5.15 W
- Type of electrical connection of main circuit (EF006819): Screw connection
- Type of control element (EF006976): Rotating button
- Device construction (EF008240): Built-in device fixed built-in technique
- With integrated auxiliary switch (EF001387): No
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
More info
▲General specifications
UL 508
IEC 60947-4-1
VDE
CSA Class No.: 3211-05
CSA File No.: 165628
CSA-C22.2 No. 60947-4-1-14
UL Category Control No.: NLRV
CE
UL
CSA
IEC/EN 60947
IEC/EN 60947-4-1
UL 60947-4-1
UL File No.: E36332
VDE 0660
Features & Functions
Motor protection
General
Also motors with efficiency class IE3
≤ 0.25 %/K, residual error for T > 40°
-5 - 40 °C to IEC/EN 60947, VDE 0660
Climatic environmental conditions
Damp heat, cyclic, to IEC 60068-2-30
Terminal capacities
2 x (1 - 6) mm², ferrule to DIN 46228, Screw terminals
2 x (0.75 - 2.5) mm², ferrule to DIN 46228, Spring-loaded terminals
1 x (0.75 - 2.5) mm², Spring-loaded terminals
1 Nm, Screw terminals, Control circuit cables
Electrical rating
Short-circuit rating
600 A, 600 V High Fault, max. Fuse, SCCR (UL/CSA)
50 kA, 600 V High Fault, Fuse, SCCR (UL/CSA)
600 A, 600 V High Fault, max. CB, SCCR (UL/CSA)
65 kA, 240 V, SCCR (UL/CSA)
65 kA, 480 Y/277 V, SCCR (UL/CSA)
Accessories required BK25/3-PKZ0-E
3.9 A, Irm, Setting range max.
Basic device fixed 15.5 x Iu, Trip Blocks
Communication