PKE32/XTU-32 121734 Y7-121734 EATON ELECTRIC Motor-protective circuit-breaker, 3p, Ir 8-32A, standard
PKE32/XTU-32
121734
Y7-121734
EATON - MOELLER
1 Pcs.
Automation > Motor protection circuit-breaker
Electronic Circuit Breakers
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A motor-protective circuit-breaker is an essential electro-mechanical device used to protect electric motors against thermal overloads, short circuits, and phase failures. Such units provide manual motor starting and stopping while ensuring comprehensive system protection in automated industrial environments.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Overload release current setting (EF002336): 32 A
- Adjustment range undelayed short-circuit release (EF007131): 496 A
- With thermal overload protection (EF006233): No
- Phase failure sensitive (EF007400): No
- Switch off technique (EF007007): Electronic
- Rated operating voltage (EF001435): 690 V
- Rated permanent current Iu (EF001389): 32 A
- Rated operation power at AC-3, 230 V (EF007025): 7.5 kW
- Rated operation power at AC-3, 400 V (EF001364): 15 kW
- Type of electrical connection of main circuit (EF006819): Screw connection
- Type of control element (EF006976): Rotating button
- Device construction (EF008240): Built-in device fixed built-in technique
- With integrated auxiliary switch (EF001387): No
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
- Degree of protection (IP) (EF005474): IP20
More info
▲General specifications
CSA
IEC/EN 60947-4-1
IEC/EN 60947
CSA Class No.: 3211-05
CSA File No.: 165628
CSA-C22.2 No. 60947-4-1-14
UL
UL File No.: E36332
UL Category Control No.: NLRV
VDE 0660
UL 60947-4-1
Features & Functions
Motor protection
Overload release
General
900 (Class 15) AC-4 cycle operation, Main conducting paths
For all combinations with an SWD activation, you need not adhere to the minimum current flow times and minimum cut-out periods.
500 (Class 5) AC-4 cycle operation, Main conducting paths
1000 (Class 20) AC-4 cycle operation, Main conducting paths
Note: Going below the minimum current flow time can cause overheating of the load (motor).
IP20
-5 - 40 °C to IEC/EN 60947, VDE 0660
Ambient conditions, mechanical
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Terminal capacities
2 x (1 - 6) mm², ferrule to DIN 46228
1 x (1 - 6) mm²
1 Nm, Screw terminals, Control circuit cables
Electrical rating
Short-circuit rating
100 A, Class J, 600 V High Fault, max. Fuse, SCCR (UL/CSA)
Delayed approx. 60 ms, Trip blocks
Basic device fixed 15.5 x Iu, Trip Blocks
± 20% tolerance, Trip blocks
Switching capacity
32 A, AC-3 up to 690 V