View larger
PKZM0-12 278486 Y7-278486 EATON ELECTRIC Motor-protective circuit-breaker, 3p, Ir 8-12A
PKZM0-12
278486
Y7-278486
EATON - MOELLER
1 Pcs.
Automation > Motor protection circuit-breaker
Circuit Breakers PKZ
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Eaton Moeller PKZM0-12 motor-protective circuit-breaker acts as a dedicated switching assembly designed to monitor and protect three-phase electric motors from phase failure, overloads, and short circuits. This type of device is typically deployed inside machinery control enclosures to ensure safe operational sequencing. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Overload release current setting (EF002336): 8 A
- Adjustment range undelayed short-circuit release (EF007131): 186 A
- With thermal overload protection (EF006233): No
- Phase failure sensitive (EF007400): Yes
- Switch off technique (EF007007): Thermomagnetic
- Rated operating voltage (EF001435): 690 V
- Rated permanent current Iu (EF001389): 12 A
- Rated operation power at AC-3, 230 V (EF007025): 3 kW
- Rated operation power at AC-3, 400 V (EF001364): 5.5 kW
- Power loss (EF005387): 6.64 W
- Type of electrical connection of main circuit (EF006819): Screw connection
- Type of control element (EF006976): Rotating button
- Device construction (EF008240): Built-in device fixed built-in technique
- With integrated auxiliary switch (EF001387): No
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
More info
▲General specifications
CSA Class No.: 3211-05
UL File No.: E36332
IEC/EN 60947-4-1
UL
UL Category Control No.: NLRV
VDE 0660
CSA File No.: 165628
CSA-C22.2 No. 60947-4-1-14
IEC/EN 60947
CE
CSA
Features & Functions
Motor protection
General
Also motors with efficiency class IE3
-25 - 55 °C, Operating range
≤ 0.25 %/K, residual error for T > 40°
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Terminal capacities
2 x (1 - 6) mm², ferrule to DIN 46228
1 x (1 - 6) mm²
1 Nm, Screw terminals, Control circuit cables
Electrical rating
Short-circuit rating
18 kA, 600 V High Fault, CB, SCCR (UL/CSA) with 600 A, 600 V High Fault, Fuse, SCCR (UL/CSA)
65 kA, 480 V High Fault, Fuse, SCCR (UL/CSA) with 600 A, 480 V High Fault, Fuse, SCCR (UL/CSA)
65 kA, 480 V High Fault, CB, SCCR (UL/CSA) with 600 A, 480 V High Fault, CB, SCCR (UL/CSA)
18 kA, 600 Y/347 V, SCCR (UL/CSA)
Accessories required BK25/3-PKZ0-E
65 kA, 480 Y/277 V, SCCR (UL/CSA)
± 20% tolerance, Trip blocks
186 A, Irm, Setting range max.