View larger
PKZM01-10 278484 Y7-278484 EATON ELECTRIC Motor-protective circuit-breaker, 3p, Ir 6.3-10A
PKZM01-10
278484
Y7-278484
EATON - MOELLER
1 Pcs.
Automation > Motor protection circuit-breaker
Circuit Breakers PKZ
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Featuring a convenient push-button actuator, the Eaton Moeller PKZM01-10 motor-protective circuit-breaker offers precise thermomagnetic trip settings for industrial drives. These compact protective units are commonly mounted directly on machine housings for rapid manual switching. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Overload release current setting (EF002336): 6.3 A
- Adjustment range undelayed short-circuit release (EF007131): 155 A
- With thermal overload protection (EF006233): No
- Phase failure sensitive (EF007400): Yes
- Switch off technique (EF007007): Thermomagnetic
- Rated operating voltage (EF001435): 690 V
- Rated permanent current Iu (EF001389): 10 A
- Rated operation power at AC-3, 230 V (EF007025): 2.2 kW
- Rated operation power at AC-3, 400 V (EF001364): 4 kW
- Power loss (EF005387): 6.48 W
- Type of electrical connection of main circuit (EF006819): Screw connection
- Type of control element (EF006976): Push button
- Device construction (EF008240): Built-in device fixed built-in technique
- With integrated auxiliary switch (EF001387): No
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
More info
▲General specifications
CSA File No.: 165628
IEC/EN 60947
UL Category Control No.: NLRV
UL File No.: E36332
CSA-C22.2 No. 60947-4-1-14
UL 60947-4-1
VDE 0660
CSA Class No.: 3211-05
UL
IEC/EN 60947-4-1
CSA
Features & Functions
Motor protection
General
Also motors with efficiency class IE3
≤ 0.25 %/K, residual error for T > 40°
-5 - 40 °C to IEC/EN 60947, VDE 0660
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Terminal capacities
2 x (1 - 6) mm², ferrule to DIN 46228
2 x (1 - 6) mm²
Electrical rating
Short-circuit rating
30 kA, 600 V High Fault, Fuse, SCCR (UL/CSA) with 600 A, 600 V High Fault, Fuse, SCCR (UL/CSA)
30 kA, 600 V High Fault, CB, SCCR (UL/CSA) with 600 A, 600 V High Fault, CB, SCCR (UL/CSA)
Basic device fixed 15.5 x Iu, Trip Blocks
± 20% tolerance, Trip blocks