Request QuoteProduct Overview
The Eaton Moeller PKZM4-63 motor-protective circuit-breaker is a heavy-duty switching device designed to safeguard larger industrial motors against electrical overloads and short circuits. These robust units ensure dependable performance and safety in demanding manufacturing applications.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Overload release current setting (EF002336): 55 A
- Adjustment range undelayed short-circuit release (EF007131): 977 A
- With thermal overload protection (EF006233): No
- Phase failure sensitive (EF007400): Yes
- Switch off technique (EF007007): Thermomagnetic
- Rated operating voltage (EF001435): 690 V
- Rated permanent current Iu (EF001389): 65 A
- Rated operation power at AC-3, 230 V (EF007025): 18.5 kW
- Rated operation power at AC-3, 400 V (EF001364): 34 kW
- Power loss (EF005387): 31.5 W
- Type of electrical connection of main circuit (EF006819): Screw connection
- Type of control element (EF006976): Rotating button
- Device construction (EF008240): Built-in device fixed built-in technique
- With integrated auxiliary switch (EF001387): No
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
More info
▲General specifications
IEC/EN 60947
UL 60947-4-1
CSA File No.: 165628
CSA-C22.2 No. 60947-4-1-14
UL Category Control No.: NLRV
UL File No.: E36332
IEC/EN 60947-4-1
CSA Class No.: 3211-05
UL
VDE 0660
CSA
Features & Functions
Motor protection
General
Also motors with efficiency class IE3
-5 - 40 °C to IEC/EN 60947, VDE 0660
≤ 0.25 %/K, residual error for T > 40°
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Terminal capacities
2 x (0.75 - 25) mm², Main cables
2 x (0.75 - 16) mm²
Electrical rating
Short-circuit rating
42 kA, 600 V High Fault, CB, SCCR (UL/CSA)
600 A, 600 V High Fault, max. CB, SCCR (UL/CSA)
600 A, 600 V High Fault, max. Fuse, SCCR (UL/CSA)
50 kA, 480 Y/277 V, SCCR (UL/CSA)
50 kA, 240 V, SCCR (UL/CSA)
1008 A, Irm, Setting range max.
Basic device fixed 15.5 x Iu, Trip Blocks