View larger
PKZM01-2,5 278481 Y7-278481 EATON ELECTRIC Motor-protective circuit-breaker, 3p, Ir 1.6-2.5A
PKZM01-2,5
278481
Y7-278481
EATON - MOELLER
1 Pcs.
Automation > Motor protection circuit-breaker
Circuit Breakers PKZ
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Compact electric motor control schemes utilize specialized motor-protective circuit-breakers to guard against thermal overloads and short circuits. These devices ensure reliable manual switching and automatic tripping for smaller industrial drives.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Overload release current setting (EF002336): 1.6 A
- Adjustment range undelayed short-circuit release (EF007131): 39 A
- With thermal overload protection (EF006233): No
- Phase failure sensitive (EF007400): Yes
- Switch off technique (EF007007): Thermomagnetic
- Rated operating voltage (EF001435): 690 V
- Rated permanent current Iu (EF001389): 2.5 A
- Rated operation power at AC-3, 230 V (EF007025): 0.37 kW
- Rated operation power at AC-3, 400 V (EF001364): 0.75 kW
- Power loss (EF005387): 5.16 W
- Type of electrical connection of main circuit (EF006819): Screw connection
- Type of control element (EF006976): Push button
- Device construction (EF008240): Built-in device fixed built-in technique
- With integrated auxiliary switch (EF001387): No
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
More info
▲General specifications
UL 60947-4-1
CSA File No.: 165628
VDE 0660
CSA Class No.: 3211-05
UL Category Control No.: NLRV
CSA
CSA-C22.2 No. 60947-4-1-14
UL File No.: E36332
IEC/EN 60947-4-1
IEC/EN 60947
CE
Features & Functions
Phase failure sensitive
General
Branch circuit: Manual type E if used with terminal, or suitable for group installations, (UL/CSA)
≤ 0.25 %/K, residual error for T > 40°
-5 - 40 °C to IEC/EN 60947, VDE 0660
Climatic environmental conditions
Damp heat, cyclic, to IEC 60068-2-30
Terminal capacities
2 x (1 - 6) mm², ferrule to DIN 46228
2 x (1 - 6) mm²
Electrical rating
Short-circuit rating
50 kA, 600 V High Fault, CB, SCCR (UL/CSA) with 600 A, 600 V High Fault, CB, SCCR (UL/CSA)
Basic device fixed 15.5 x Iu, Trip Blocks
± 20% tolerance, Trip blocks