View larger
PKZM01-20 283383 Y7-283383 EATON ELECTRIC Motor-protective circuit-breaker, 3p, Ir 16-20A
PKZM01-20
283383
Y7-283383
EATON - MOELLER
1 Pcs.
Automation > Motor protection circuit-breaker
Circuit Breakers PKZ
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller PKZM01-20 is a motor-protective circuit-breaker engineered to safeguard three-phase electric motors against thermal overloads and short circuits. These protective devices are standard in control panels to ensure safe motor starting, running, and stopping operations. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Overload release current setting (EF002336): 16 A
- Adjustment range undelayed short-circuit release (EF007131): 310 A
- With thermal overload protection (EF006233): No
- Phase failure sensitive (EF007400): Yes
- Switch off technique (EF007007): Thermomagnetic
- Rated operating voltage (EF001435): 690 V
- Rated permanent current Iu (EF001389): 20 A
- Rated operation power at AC-3, 230 V (EF007025): 5.5 kW
- Rated operation power at AC-3, 400 V (EF001364): 9 kW
- Power loss (EF005387): 5.82 W
- Type of electrical connection of main circuit (EF006819): Screw connection
- Type of control element (EF006976): Push button
- Device construction (EF008240): Built-in device fixed built-in technique
- With integrated auxiliary switch (EF001387): No
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
More info
▲General specifications
UL 60947-4-1
UL File No.: E36332
CSA File No.: 165628
CE
CSA
UL Category Control No.: NLRV
CSA Class No.: 3211-05
VDE 0660
IEC/EN 60947
IEC/EN 60947-4-1
UL
Features & Functions
Motor protection
General
Branch circuit: Manual type E if used with terminal, or suitable for group installations, (UL/CSA)
-5 - 40 °C to IEC/EN 60947, VDE 0660
-25 - 55 °C, Operating range
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Terminal capacities
2 x (1 - 6) mm²
Electrical rating
Short-circuit rating
10 kA, 600 V High Fault, CB, SCCR (UL/CSA) with 125 A, 600 V High Fault, CB, SCCR (UL/CSA)
18 kA, 600 V High Fault, Fuse with CL, SCCR (UL/CSA) with 600 A, 600 V High Fault, Fuse with CL, SCCR (UL/CSA)
18 kA, 600 V High Fault, CB with CL, SCCR (UL/CSA) with 600 A, 600 V High Fault, CB with CL, SCCR (UL/CSA)
18 kA, 480 V High Fault, CB, SCCR (UL/CSA) with 600 A, 480 V High Fault, CB, SCCR (UL/CSA)
18 kA, 480 V High Fault, Fuse, SCCR (UL/CSA) with 600 A, 480 V High Fault, Fuse, SCCR (UL/CSA)
± 20% tolerance, Trip blocks
310 A, Irm, Setting range max.