Request QuoteProduct Overview
A PKZM01-1,6 Eaton Moeller motor-protective circuit-breaker is a specialized switching device built to defend small industrial motors from thermal overloads and electrical faults. These devices are widely used in manufacturing automation to ensure safe motor startup and continuous operational protection. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Overload release current setting (EF002336): 1 A
- Adjustment range undelayed short-circuit release (EF007131): 25 A
- With thermal overload protection (EF006233): No
- Phase failure sensitive (EF007400): Yes
- Switch off technique (EF007007): Thermomagnetic
- Rated operating voltage (EF001435): 690 V
- Rated permanent current Iu (EF001389): 1.6 A
- Rated operation power at AC-3, 230 V (EF007025): 0.25 kW
- Rated operation power at AC-3, 400 V (EF001364): 0.55 kW
- Power loss (EF005387): 5.36 W
- Type of electrical connection of main circuit (EF006819): Screw connection
- Type of control element (EF006976): Push button
- Device construction (EF008240): Built-in device fixed built-in technique
- With integrated auxiliary switch (EF001387): No
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
More info
▲General specifications
CSA Class No.: 3211-05
UL Category Control No.: NLRV
VDE 0660
UL
UL 60947-4-1
CSA-C22.2 No. 60947-4-1-14
UL File No.: E36332
CSA File No.: 165628
IEC/EN 60947-4-1
IEC/EN 60947
CSA
Features & Functions
Motor protection
General
Branch circuit: Manual type E if used with terminal, or suitable for group installations, (UL/CSA)
≤ 0.25 %/K, residual error for T > 40°
-5 - 40 °C to IEC/EN 60947, VDE 0660
Climatic environmental conditions
Damp heat, cyclic, to IEC 60068-2-30
Terminal capacities
1 x (1 - 6) mm², ferrule to DIN 46228
2 x (1 - 6) mm²
Electrical rating
Short-circuit rating
50 kA, 600 V High Fault, CB, SCCR (UL/CSA) with 600 A, 600 V High Fault, CB, SCCR (UL/CSA)
Basic device fixed 15.5 x Iu, Trip Blocks
± 20% tolerance, Trip blocks