View larger
PKZM0-0,63-C 229672 XTPRCP63BC1NL EATON ELECTRIC Motor-protective circuit-breaker, 3p, Ir 0.4-0.63A, spring ..
PKZM0-0,63-C
229672
XTPRCP63BC1NL
EATON - MOELLER
1 Pcs.
Automation > Motor protection circuit-breaker
Circuit Breakers PKZ
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller PKZM0-0,63-C motor-protective circuit-breaker delivers precise electrical isolation and integrated thermal protection for low-amperage industrial motor applications. Facility engineers install these dependable three-pole switches to protect compact machinery from unexpected operational stalls and phase imbalances. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Manufacturer: Eaton Moeller
- Manufacturer part number: PKZM0-0,63-C
- Catalogue code: 229672
- Catalogue title: PKZM0-0,63-C 229672 XTPRCP63BC1NL EATON ELECTRIC Motor-protective circuit-breaker, 3p, Ir 0.4-0.63A, spring ..
- Product description: General specifications Product Name Eaton Moeller series PKZM0 Motor-protective circuit-breaker Catalog Number 229672 Model Code PKZM0-0,63-C EAN 4015082296728 Product Length/Depth 76 mm Product Height 93 mm Product Wid
- Manufacturer summary: Motor-protective circuit-breaker, 3p, Ir=0.4-0.63A, spring clamp connection Motor Protective Switch 3 poles Ir=0.4-0.63 A Connection To
More info
▲General specifications
IEC 60947-4-1
UL 508
VDE
CSA File No.: 165628
CSA-C22.2 No. 60947-4-1-14
IEC/EN 60947
UL 60947-4-1
UL Category Control No.: NLRV
CSA
UL File No.: E36332
VDE 0660
CSA Class No.: 3211-05
IEC/EN 60947-4-1
CE
UL
Features & Functions
Motor protection
General
Branch circuit: Manual type E if used with terminal, or suitable for group installations, (UL/CSA)
-25 - 55 °C, Operating range
≤ 0.25 %/K, residual error for T > 40°
Climatic environmental conditions
Damp heat, cyclic, to IEC 60068-2-30
Terminal capacities
1 x (0.75 - 2.5) mm², ferrule to DIN 46228, Spring-loaded terminals
2 x (0.75 - 2.5) mm², Spring-loaded terminals
Electrical rating
Short-circuit rating
600 A, 600 V High Fault, max. CB, SCCR (UL/CSA)
600 A, 600 V High Fault, max. Fuse, SCCR (UL/CSA)
50 kA, 600 V High Fault, Fuse, SCCR (UL/CSA)
65 kA, 240 V, SCCR (UL/CSA)
50 kA, 600 Y/347 V, SCCR (UL/CSA)
Accessories required BK25/3-PKZ0-E
± 20% tolerance, Trip blocks
9.8 A, Irm, Setting range max.