View larger
PKZM01-0,63 278478 Y7-278478 EATON ELECTRIC Motor-protective circuit-breaker, 3p, Ir 0.4-0.63A
PKZM01-0,63
278478
Y7-278478
EATON - MOELLER
1 Pcs.
Automation > Motor protection circuit-breaker
Circuit Breakers PKZ
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A Eaton Moeller Motor-protective circuit-breaker, 3p, Ir 0.4-0.63A protects low-current machinery by swiftly interrupting power when abnormal operating conditions arise. Facilities depend on these compact circuit protection devices to safeguard sensitive automated equipment and small drives from electrical hazards.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Overload release current setting (EF002336): 0.4 A
- Adjustment range undelayed short-circuit release (EF007131): 9.8 A
- With thermal overload protection (EF006233): No
- Phase failure sensitive (EF007400): Yes
- Switch off technique (EF007007): Thermomagnetic
- Rated operating voltage (EF001435): 690 V
- Rated permanent current Iu (EF001389): 0.63 A
- Rated operation power at AC-3, 230 V (EF007025): 0.09 kW
- Rated operation power at AC-3, 400 V (EF001364): 0.12 kW
- Power loss (EF005387): 5.16 W
- Type of electrical connection of main circuit (EF006819): Screw connection
- Type of control element (EF006976): Push button
- Device construction (EF008240): Built-in device fixed built-in technique
- With integrated auxiliary switch (EF001387): No
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
More info
▲General specifications
IEC/EN 60947-4-1
UL Category Control No.: NLRV
IEC/EN 60947
CSA Class No.: 3211-05
UL
CSA File No.: 165628
CSA-C22.2 No. 60947-4-1-14
UL 60947-4-1
CSA
UL File No.: E36332
VDE 0660
Features & Functions
Motor protection
General
Branch circuit: Manual type E if used with terminal, or suitable for group installations, (UL/CSA)
-5 - 40 °C to IEC/EN 60947, VDE 0660
≤ 0.25 %/K, residual error for T > 40°
Climatic environmental conditions
Damp heat, cyclic, to IEC 60068-2-30
Terminal capacities
2 x (1 - 6) mm², ferrule to DIN 46228
1 x (1 - 6) mm²
Electrical rating
Short-circuit rating
50 kA, 600 V High Fault, CB, SCCR (UL/CSA) with 600 A, 600 V High Fault, CB, SCCR (UL/CSA)
Basic device fixed 15.5 x Iu, Trip Blocks
± 20% tolerance, Trip blocks